Loading...
HomeMy WebLinkAbout52589-Z hO��pF SOUTyo`o Town of Southold * * P.O. Box 1179 ao4 53095 Main Rd Southold, New York 11971 CERTIFICATE OF OCCUPANCY No: 46974 Date: 04/15/2026 THIS CERTIFIES that the building EV CHARGER Location of Property: 5325 Rocky Point Rd East Marion, .NY 11939 Sec/Block/Lot: 21.-1-7 Conforms substantially to the Application for Building Permit heretofore,filed in this office dated: 11/13/2025 Pursuant to which Building Permit No. 52589 and dated: 01/05/2026 Was issued, and conforms to all of the requirements of the applicable provisions of the law. The occupancy for which this certificate is issued is: Two Tesla power wall units for energy storage to a single-family dwelling as applied for. Maintain clearances as required per manufacturer. The certificate is issued to: Elias Aliprandis, Tjoyia Aliprandis, Theodore Allen ,Alexandra Aliprandis Of the aforesaid building. SUFFOLK COUNTY DEPARTMENT OF HEALTH APPROVAL: ELECTRICAL CERTIFICATE: 116496 3/3/2026 PLUMBERS CERTIFICATION: A tho 'Ue Signat e �aof SOOryO TOWN OF SOUTHOLD BUILDING DEPARTMENT `� • �� SOUTHOLD, NY BUILDING PERMIT (THIS PERMIT MUST BE KEPT ON THE PREMISES WITH ONE SET OF APPROVED PLANS AND SPECIFICATIONS UNTIL FULL COMPLETION OF THE WORK AUTHORIZED) Permit#: 52589 Date: 01/05/2,026 Permission is hereby granted to: Elias Aliprandis 1 Flag Ln Manhasset Hills, NY 11040 To: Install two Tesla power wall units for energy storage to a single-family dwelling as applied for per manufacturers specifications. Premises Located at: 5325 Rocky Point Rd, East Marion, NY 11939 SCTM#21.4-7 Pursuant to application dated 11/13/2025 and approved by the Building Inspector. To expire on 01/05/2028. Contractors: Required Inspections: Fees: Battery Storage $100.00 CO-RESIDENTIAL $100.00 Total S200.00 Building Inspector APR - 1 2026 NASSAU ELECTRICAL SUFFOLK INSPECTORS 159 Route 25A,Building 1 Suite B Miller Place,NY 11764 Telephone:631 495 8136 • Fax:631 509 4538 • E-Mail:Requests@SuffolkBEI.com CERTIFICATE OF ELECTRICAL COMPLIANCE Applicant: Testa Energy Inc Jason Kane Certificate No.: 116496 Rough In Inspection Date: Final Inspection Date: Mar 03,2026 Application No.: Building Permit No.: 52589 County Tax Map No.: 1000 021.00 01.00 007.000 This Certificate of Electrical Compliance is limited to the inspection and compliance of electrical equipment and/or work described below,installed on behalf of the applicant named above,located at the premise of and not after the final inspection date above: Owner: Elias AI[prandis Site Location: 1193236,5325 Rocky Point Rd.,East Marion,NY 11939 Owner's Address(if different): 0 Residential 0 Indoor ❑Basement O Service ❑Shed ❑Commercial 0 Outdoor ❑First Floor ❑Pool ❑Hottub O New 0 Renovation ❑Second Floor O Attic ❑Garage ❑Addition ❑Survey 0 PV Solar ❑Generator ❑Conversion - — — --- ..-...-------------- O Signs 0 Battery Storage 0 Safety Inspection Other: ......._... -.-..... INVENTORY Single Phase Heat Duplex Recpt Ceiling Fixture Dual Func Breaker Three Phase Hot Water GFCI Recpt Wall Fixture Smoke Main Panel AC Cond Single Recpt Recessed Fixture CO Detect Sub Panel AC Blower Range Recpt LED Lighting Smoke CO Combo Transformer Appliance Ckt Dryer Recpt Emergency Time Clock Disconnect 1� Switches Twist Lock 0 Exit Fixtures 0 Pumps GFCI Breaker 0 Heat Pump Electric Heat Pool Luminaire 0 Exhaust Fan Other Equipment:Battery System Size:27 kWh Qty:1 Desc:Tesla Powerwall 3[240V]#1707000-XX-Y 11.5 kW/13.5 kWh Qty:1 Desc:Powerwall 3 Expansion Tesla Inc [240VI#1807000-XX-Y 13.5 kWh The electrical work and/or equipment described above were inspected and was found to be in compliance with local, state and national electrical code requirements and this office. Applicant: Tesla Energy Inc Jason Kane License No.: 51331-ME Date Printed: Mar 03,2026 Inspected By:Joe Coppola ^ Signature: p'Y pF 50blyOlo TOWN OF SOUTHOLD BUILDING DEPT. 631-765-1802 INSPECTION [ ] FOUNDATION 1ST/ REBAR [ ] ROUGH PLBG. [ ] FOUNDATION 2ND [ IN LATION/CAULKING [ ] FRAMING /STRAPPING [ ] FINAL 05-S [ ] FIREPLACE & CHIMNEY [ ] FIRE SAFETY INSPECTION [ ] FIRE RESISTANT CONSTRUCTION [ ] FIRE RESISTANT PENETRATION [ ] ELECTRICAL (ROUGH) [ ] ELECTRICAL (FINAL) [ ] CODE VIOLATION [ ] PRE C/O [ ]. RENTAL REMARKS: C7k 4e C' DATE .446 ANSPECTOR FIELD INSPECTION REPORT DATE COMMENTS � b FOUNDATION (1ST) zo It -------------------------------------- FOUNDATION (2ND) s 1 z 0 N vl y ROUGH FRAMING& PLUMBING v `� 1 T r INSULATION PER N.Y. STATE ENERGY CODE •a (0% c.a. vs �s FINAL /�[- ADDITIONAL COMMENTS PW /D�� Q-2VV s- re c-V /1/50 7 Z m m � O z C7 �d 3�5"fFQ��c4� TOWN OF SOUTHOLD—BUILDING DEPARTMENT Town Hall Annex 54375 Main Road P. O. Box 1179 Southold,NY 11971-0959 Telephone (631) 765-1802 Fax (631) 765-9502 https://www,.southoldtowliny.,gov Date Received APPLICATION FOR BUILDING PERMIT For Office Use Only F PERMIT N0. �� c�� Building Inspector: ,',� U NOV 1 3 2025 Applications and forms must be filled out in their entirety.Incomplete applications will not be accepted. Where the Applicant is not the owner,an 7 Owners Authorization form(Page 2)shall be completed. ` ' , •;,:' _1 Date: i o2Q OWNER(S)OF PROPERTY: Name: Elias Aliprandis SCTM#s000- 1000-021.00-01.00-007.000 v - Project Address:- 5325 Rocky Point Rd East Marion, NY 11939 t Phone#: (516) 672-7625 Email: elias.aliprandis@gmail.com Mailing Address: 5325 Rocky Point Rd East Marion, NY 11939 CONTACT PERSON: Name: Patti Zullo/Tim Hand Mailing Address:15 Grumman Rd West Suite 400 Bethpage NY 11714 �- Phone#:631-636-4277 I- Email-BethpagePlC@tesla.com DESIGN PROFESSIONAL INFORMATION: Name: u h I t` Mailing Address: 5 chr �elU�� ' Dint h IrU Phone#: 00 , a 0 a q50 Email:/i h is o) r , CO M CONTRACTOR INFORMATION: C� ,. Name: TESLA ENERGY OPERATIONS INC Tim Hand/Patti Zullo 10 Mailing Address:15 Grumman Rd West Suite 400 Bethpage NY 11714 Phone#:631-636-4277 TEmTil:BethpagePlC@tesl'a.com DESCRIPTION OF PROPOSED CONSTRUCTION ❑New Structure ❑Addition ❑Alteration ❑Repair ❑Demolitio` Estimated Cost of Proj16 �Other Installation or: home energystorage system a e �i Will the lot be re-graded? ❑Yes ANo Will excess fill be removed from premises? ❑Yes No 1 1000- n3t I a _ 0 —0()7, OO 0 PROPERTY INFORMATION Existing use of property: Residential one faMily Intended use of property: Residential one family Zone or use district in which premises is situated: Are there any covenants and restrictions with respect to this property? ❑Yes *No IF YES, PROVIDE A COPY. . 8 Check Box After Reading: The owner/contractor/design.professional is responsible for all drainage and storm water issues as provided by Chapter 236 of the Town Code.APPLICATION IS HEREBY MADE to the Building Department for the issuance of a Building Permit pursuant to the Building Zone Ordinance of the Town of Southold,Suffolk,County,New York and other applicable Laws,Ordinances or.Regulations,for the construction of buildings, additions,alterations or for removal or demolition as herein described.The applicant agrees to comply with all applicable laws,ordinances,building code, housing code and regulations and to admit authorized inspectors on premises and in,building(s)for necessary inspections.False statements made herein are punishable as a Class A misdemeanor pursuant to Section 210.4S of the New York State Penal Law. Application Submitted By(print name).:Tim Hand ®Authorized Agent ❑Owner Signature of Applicant: � G'x G Date: STATE OF NEW YORK) �J SS: COUNTY OF Nassau ) TimothyHand being duly sworn, deposes and says that(s)he is the applicant (Name of individual signing contract) above named, (S)heisthe Contractor/Agent Tesla Energy Operations Inc (Contractor, Agent, Corporate Officer, etc.) of said owner or owners, and is duly authorized to perform or have performed the said work and to make and file this application;that all statements contained in this application are true to the best of his/her knowledge and belie d nd a that the work will be performed in the manner set forth in the application file therewith. >- N w p w c Sworn before me this 0 o N O w Y N ID day of -V4 INS�-4' 20 d o a o Public Q c~n N c) w S ~ m O VJ Q d Z PROPERTY OWNER AUTHORIZATION 3 (Where the applicant is not the owner) o z Elias Ali randis I, p residing at 5325 Rocky Point Rd East Marion, NY 11939 C Tesla Energy Operations Inc/Tim Hand do hereby authorize to apply on aJ my behalf to the Town of Southold Building Department for approval as described herein. Owner's Signature Date Elias Aliprandis Print Owner's Name 2 s+ o t T = 5 L n Energy Price Override Tool --- - - r Elias Aliprandis Job Number:JB-1193236-00 elias.aliprandis@gmail.com Reservation Number: EN8853960 5325 Rocky Point Rd, East Marion, NY 11939, USA Offer Type: ENERGY_LOAN PSE&G-Long Island (999475) Credit Decision: APPROVED g Application Status: CONFIRMED 'owerwall Design+2 Units+1 Gateway Primar Created:11/5/2025 :ustom Create New Quote Pricing 08/10/20 'owerwall Design+2 Units+1 Gateway Created:10/31/2025 ;ustom Create New Quote Pricing 08/10/20 Quote Confirmed:11/3/2025 Pricing 08/10/2025 )werwall System Cost 1 Powerwall 3 $8,200.00 1 Expansion Pack $5,900.00 Accessories $200.00 Deployment Fee $7,200.00 1 Powerwall Gateway $900.00 Installation Efficiency Adjustment -$1,800.00 Tax $0.00 Subtotal $20,600.00 iyment Details Deposit $100.00 Subtotal $100.00 abates to Customer US Federal Tax Credit-30% $6,180.00 rtal Contract Price 0 AM Amount Due $20,600.00 Bt Cost ilance After Payments $20,500.00 Contract-15029163 CASH Unsigned Created:11/3/2025 Sent by: hilldan Contract-15029165 LOAN3 Accepted Created:11/3/2025 Sent by: hilldan i Contract-15029166 LOAN4 Unsigned Created:11/3/2025 Sent by: hilldan Contract-15029167 LOAN5 Unsigned Created:11/3/2025 Sent by: hilldan 1 Tesla Road,Austin,TX 78725 - P 650 6815100 F 650 6815101 Version#9.6 November 6, 2025 RE: Powerwall Certification letter Project/Job# 1193236 Project Address: Aliprandis Residence 5325 Rocky Point Rd East Marion, NY 11939 AHJ Southold Town Tesla Office Bethpage To Whom it may concern: The installation manual for the Tesla Powerwall was reviewed for wall mounting considerations. Based on the weight of the unit and the attachment layout of the mounting bracket, it was determined that the following fasteners should be used: For mounting to walls with wood studs with the PW suspended above the ground: 4- 1/4 in.Wood Screws with a minimum embedment of 2.5" In addition,the wall structure has been verified as sufficient to support the additional load imposed by the Tesla PowerWall unit. (�OF NEW), Sincerely, �P ,t KA 0 Tesla Energy r — � C7 _ Lu �O 0954 0 100 °NPR Applicable Codes: IBC 2018,ASCE 7-16 000 8 0' 0' ROM Wall Height 8.0 ft. Stud Size 1.5 x 3.5 Stud Spacing 16 in. O.C. Lumber Type DF Stud Trib. Roof Loading 10.0 ft. • 0 1 D �' 0 0 0 D i 0 O D DL, LL, $L PSF(DL adjusted for pitch) Compression Stress(PSI) DL LL SL DL LL SL Roof 10.5 20.0 21.0 26.7 0.0 53.3 Ceiling 5.0 12.7 First Floor Wall 8.5 17.3 Second Floor&Ceiling 8.0 40.0 20.3 101.6 Second Floor Wall 8.5 17.3 Nor '0 ' 0 D i PowerWall Dead Load(Including Brackets) 300 Ibs No.Stacked PowerWall Units 1 Note: PW suspended Dead Load per Stud No. Studs 2 150 Ibs above the ground Resulting Axial Stress = , Eccentric Moment Total 2265 Ibs-in Moment per Stud No.Studs 2 1133 Ibs-in Resulting Bending Stress O Wind Speed(ULT) 130 mph Risk Category 2 Exposure Category C PowerWall Elevation 0-15 ft. Distance of PowerWall(s)to Corner of Building 3.0 ft. Directionality Factor 0.85 Topographic Factor 1.00 Velocity Pressure Exposure Coefficient 0.85 Resulting Bending Stress • 0 8 0 0.0own Component Amplification Factor ah 1.00 Soil Site Class D Component Response Modification Factor RP 2.5 SRA at Short Period SS 0.200 Component Importance Factor Ip 1.00 SRA at 1s Period Sl 0.045 Component Operating Weight Wp 300.0 Ibs Wall Dead Load 8.50 psf Wall Bending Stress Battery Axial Stress Battery Bending Stress = /orb Eccentric Battery Stress — � i Governing Load Combo DL LL SL W E Total D+.75L+.75(.6W)+.75S 123 psi 76 psi 40 psi -- --- 239 psi ®: @ Governing Load Combo DL LL SL W E Total D+.75L+,75(.6W)+.75S 185 psi --- --- 365 psi --- 549 psi 0 @ 0 0 0 @ 0 0 Governing Load Combo =DL LL SL W E Total D+W 185 psi --- --- 956 psi -- 1141 psi Load Duration Factor CD = 1.60 Repetive Member Factor C, = 1.15 Size Factor: Bending Size Factor:Compression Cr = 1.10 CF = 1.05 Based on NDS Eqn.3.9-3.... F, = 850.0 psi 0.91 <= 1.05 Pass Fb = 700.0 psi E = 1400000.0 psi Based on NDS Eqn,3.9-4.... Emin = 510000.0 psi 0.04 <= 1.05 Pass 0 @ 0 0@ @ e e FB. = 1141 psi F'bl = 1417 psi / / FEEo; r/0 ' 0 Fastener Type 1/4 in.Wood Screw #Top Fasteners 2 Fastener Diameter 0.25 in. #Bottom Fasteners 2 Fastener Area 0.049 sq.in. Total Fasteners 4 Vertical Distance Between Fasteners 19.75 in. �•. a o.¢ roe :o a PowerWall Battery Version PW3 PowerWall Battery Weight 300.0 lbs No.Stacked PowerWall Units 1 Panel Depth 7.60 in. Wall Finish Depth 1.00 in. Half Panel Depth 3.80 in. Total Wall Depth 3.50 in. Frame Depth 1.00 in. Half Wall Depth 1.75 in. Total Eccentricity = 7.55 in. Eccentricity Moment = 2265 Ibs-in T and C Components = 115 Ibs/fastener row T per Fastener Shear per Fastener = / a a Approximate Battery Wind Load 43.76 psf Dimensions Width 24.00 in. Height 43.50 in. Surface Area 71044.00 sq. in. Suction Force = 317 Ibs Tension per Lag Seismic Vertical 10 Ibs Moment 72 Ibs-in Shear per lag 2 Ibs IT and C Components 4 Ibs/fastener row Seismic Vertical = 10 Ibs Seismic Horizontal = 17 Ibs Withdrawal per la = %���%� '%/ From Horizontal F V per fastener = j � From Vertical FP /, T per fastener _ //�j �j�� From Vertical Fp Eccentricity(top fasteners only) / Governing Load Combo DL LL SL W E Total D 75lbs --- --- --- --- 75lbs Governing Load Combo DL LL SL W E Total D 57lbs --- --- --- --- 57lbs Withdrawal Load W = 57 Ibs Shear Load Z = 75 Ibs Load Duration Factor CID = 0.90 W. = 387 Ibs Z' = 146 Ibs a = 37.40 p = 2.50 in. R = 94 Ibs Z'a = 189 Ibs 10 17/100/10/ q off. } • °°` �� ; �W dye • � ��;�� +,tea;, -sr .7�# � „z P�6 � ° • • F N. �:b"�aQ�v 4� d A a h • . r ��a„b 4� �4 � 'fie •° • _;.�$**�� "r,� s q°t� ,gyp-��.��,�k ��µ��°� °� i, ° 4 Introduction Tesla Powerwall 3 was tested by Intertek Testing Services NA, Inc., an ISO 17025 accredited laboratory and Nationally Recognized Testing Laboratory (NRTL). The testing laboratory was provided by ESRG (Energy Service Response Group), also ISO 17025 accredited. Testing was conducted in November 2022 in accordance with ANSI/CAN/UL 9540A:2019 Fourth Edition, Dated November 12, 2019 - Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems. This supplemental guide is intended to aid Authorities Having Jurisdiction (AHJs) in the application of the test results to determine compliance with applicable codes. Specifically, it is intended for use where building and/or fire codes require large-scale fire test data to support deviations from the minimum requirements set forth in those codes. The Tesla Powerwall 3 has met the unit level performance criteria outlined in ANSI/CAN/UL 9540A when installed as follows: • The Powerwall must be installed in accordance with the manufacturer's installation instructions • No additional non-combustible substrate is required • Where applicable, a minimum clearance of 1" on the side(s) of the unit is required to mitigate the risk of side-to-side propagation to adjacent Powerwall 3 units and walls • The Powerwall 3 manufacturer installation instructions require a minimum lateral separation of 4" between units Page and Section numbers referenced from the test report are presented in bold type. For example, verification that the Tesla Powerwall 3 has met the performance criteria outlined in ANSI/CAN/UL 9540A can be found on pages 17 through 20 of the report. For ease of use, this guide is arranged to follow the sequence used in the report issued by Intertek titled Test Report ANS1/CAN/UL 9540A:2019. The scope of the report includes the performance criteria outlined in Section 9 - Unit Level Testing of ANSI/CAN/UL 9540A: 2019 Fourth Edition. The report also includes a summary of data acquired at the cell and module levels during prior testing. All Section numbers in the report are references to ANSI/CAN/UL 9540A:2019 Fourth Edition, Dated November 12, 2019. 2023 Powerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental Guide 2 Product Details The device under test (DUT) in the attached report is the Tesla Powerwall 3, model 1707000-XX-Y, which integrates Energy Storage System (ESS) into an all-in-one Solar PV and Storage solution with a storage capacity of 13.5 kWh. Full product specifications and certifications are available on request from all Tesla authorized installers. Unit Label TESLA POWERWALL ENERGY STORAGE SERIAL NO SYSTEM GRID SUPPORT UTILITY DATAMATRIX INTERACTIVE&STANDALONE INVERTER TESLA PART NO.1707000-XX-Y SN:XXXXXXXXXX BATTERY ENERGY STORAGE SYSTEM(BESS)& PHOTOVOLTAIC(PV)POWER CONVERSION EQUIPMENT NOMINAL BATTERY ENERGY 13.5 KW-HR BATTERY TYPE LI-ION PROTECTIVE CLASS CLASS I ENCLOSURE TYPE NEMA3R OPERATING TEMPERATURE RANGE -20°C TO 50°C DE-RATED TEMPERATURE RANGE 40°C TO 50°C PV INVERTER TOPOLOGY NON-ISOLATED BESS INVERTER TOPOLOGY ISOLATED MASS 130 KG BATTERY ENERGY STORAGE SYSTEM(BESS)& PHOTOVOLTAIC(PV)SPECIFICATIONS NOMINAL GRID VOLTAGE INPUT&OUTPUT 240 V(AC) GRID VOLTAGE RANGE 211 V-264 V(AC) PHASE 2W+N+PE FREQUENCY 60Hz MAX SUPPLY FAULT CURRENT 10 kA(AC) ❑ 24A(AC) (5.8 KVA) MAX CONTINUOUS OUTPUT ❑ 32A(AC) (7.7 KVA) CURRENT(POWER AT 240V) ❑ 40A(AC) (9.6 KVA) ❑48A(AC) (11.5 KVA) BESS MAX CONTINUOUS INPUT CURRENT 20.8 A(AC) BESS MAX CONTINUOUS INPUT POWER 5 kVA POWER FACTOR -1 TO+1 PV OPERATING DC INPUT VOLTAGE RANGE 60-550 V(DC) PV OPERATING DC MPPT VOLTAGE RANGE 150-480 V(DC) PV MAX SYSTEM VOLTAGE 600 V(DC) PV MAX INPUT CURRENT 13 A(DC) PV DC ARC FAULT PROTECTION TYPE 1 CONFORMS TO UL STD 9540,UL STD 1741,UL STD 1973,UL STD 16996 CONTAINS FCC ID:2AEIM-WLI8DBMOD,XMR2020BG95M2 CONTAINS IC: 20098-WLI8DBMOD, 10224A-2020BG95M2 THE MAXIMUM OPERATING CURRENT OF THIS SYSTEM MAY BE CONTROLLED ELECTRONICALLY.REFER TO THE MANUFACTURER'S INSTRUCTIONS FOR MORE INFORMATION. 2023 Powerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental Guide 3 Summary of Results A comprehensive summary of the required information that must be included in the unit level test report is provided beginning on page 13 of the test report. This section provides important information needed to determine residential and fire code compliance where reduced minimum separation distances are permitted, and where the unit is intended to be installed on a combustible substrate. Final verification that the Tesla Powerwall 3 has met the performance criteria outlined in ANSI/CAN/UL 9540A can be found on pages 17 through 20 of the report. This portion of the 'report can be used as a checklist to aid in the verification of the unit's conformance to the performance criteria for the intended installation configurations. Table 9.1 from the test report is divided into two parts, residential and non- residential installations. It is important to note that Tesla Powerwall 3 was only evaluated for residential installations under the scope of this testing. In the unit level test, it was demonstrated that: • The Powerwall 3 enclosure provides adequate thermal protection from the wall surface on which it is mounted. Wall surface temperatures did not exceed 97°C (175°F) of temperature rise above ambient per 9.2.15 of the test standard; as such, additional substrate is not required • Thermal runaway did not propagate past (1) target cell • Large scale fire testing was conducted with 1" lateral unit spacing to represent worst-case scenario conditions. Testing showed the risk of unit-to-unit propagation to adjacent units is mitigated with 1" unit spacing • Manufacturer installation instructions dictate 4" minimum lateral spacing between units to',maintain proper airflow during normal operation. Figure 1: Photo 2 from Test Report Displaying Test Set Up 2023 Powerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental Guide 4 Cell Level Construction General product details, including cell and module level construction and Tests information, are outlined on pages 5 and 6 of the test report. Pages 5 and 37 of the report provide background information and data collected during cell and module-level testing previously conducted. This data does not directly correlate to residential or fire code requirements; rather, it is used to document and compare the characteristics of different cell chemistries and module designs. One important value recorded is the temperature at which thermal runaway occurs. This value is determined in accordance with 7.3.1.9 of the test standard. This temperature of 1880C is used to verify that an internal fire condition has been established during the Unit Level test. Construction Details: Cell Level Powerwall 3 utilizes Lithium Iron Phosphate/Graphite chemistry based prismatic cells. Cell dimensions, weight and electrical characteristics are noted on page 5 of the test report. Figure 2: Photo 1 from Test Report Displaying an Individual Cell Performance Criteria: Cell Level Application of heat using film heater methodology did result in a thermal runaway condition; therefore, module level testing was required (page 37 of the test report) Cell surface temperature at venting: 1740C Cell surface temperature at runaway: 1880C 2023 Powerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental Guide 5 Module Level Construction and Tests Construction Details: Powerwall 3 consists of a single module with, cells positioned within Module Level a metallic semi-open enclosure. The Powerwall 3 module is designed without a fully encapsulated metallic enclosure to allow vent gases to be routed in such a way that increases the overall propagation resistance of the module; this prevents a dangerous buildup of gases that could lead to an explosion or deflagration hazard. The module consists of 26 cells electrically wired in series and arranged in two rows of (13) prismatic cells; this information can be found on page 5 of the test report. Figure 3: Illustration 2 from Test Report Depicting the Layout of Cells in the Module Performance Criteria: Application of heat using film heater methodology did result in Module Level a thermal runaway condition, and the resulting event was not contained by the module design; therefore, unit level testing was required. 2023 Powerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition rest Report Supplemental Guide 6 Unit Level Test: General Section 9: Unit Level Testing information begins on page 7 of the report. In additional to providing greater detail on the test setup and unit performance, this portion of the report can also be used as a checklist to aid in the verification of the testing/aboratorv's conformance to the test procedure. Sample and Test Configuration ANSI/CAN/UL 9540A provides for several configurations: • Residential and non-residential use cases • Wall and floor mounting • Indoor and outdoor locations Tested Configuration Testing was conducted using a single indoor wall-mounted test configuration that was determined to be representative of all intended installation configurations.Tesla Powerwall 3 is intended to be installed in any of the configurations noted below (Section 9.1.1 of the test report): • Indoor floor-mounted residential use BESS • Outdoor ground-mounted residential use BESS • Outdoor wall-mounted residential use BESS • Indoor wall-mounted residential use BESS The testing configuration was adapted to include the characteristics necessary to be an accurate representative test case for the above listed scenarios. This determination was made by the testing laboratory based on allowable installation scenarios for Powerwall 3 in conjunction with rigorous pre-test planning, component level review of the BESS unit construction, integral thermal runaway mitigating factors, and cell level chemistry. • In accordance with Section 9.1.2 of the test standard, the indoor floor-mounted test is considered representative of the outdoor ground-mounted test with the incorporation of a 1-ft soffit. • Section 9.1.2 of the test standard dictates all testing is to be done indoors with distances between'in itiati ng and target units being representative of the intended installation scenario. • Tesla Powerwall 3 unit to unit spacing is agnostic of the installation configuration. • Worst case representative testing conducted with 1" unit to unit spacing; manufacturer installation instructions dictate 4" minimum unit to unit spacing. 2023 Powerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental'Guide 7 Tested Configuration: Testing was conducted in a standard NFPA 286 fire test room, with Unit Level Test the test room being 12 x 8 x 8-ft high with a 2.5 x 7.5-ft high opening. Walls were covered with standard 5/8" gypsum board which was painted black in accordance with Section 9.2.6 of the test standard. y xg Figure 4: Photo 5 from Test Report Figure 5: Photo 3 from Test Displaying Room Used for Testing Report of Test Configuration Units were installed on an instrumented wall with (16) thermocouples running the length of the wall, with 6" spacing between thermocouples. The south wall of the room was similarly instrumented with (16) thermocouples, and (2) thermocouples were placed in the ceiling. Approx.thermocouple Q East Wall 15 High Q South Wall 15 High locations depicted Q Q O--1 O 6" O—J O O O O O O O O O C North Target 1 highC Q South Target 1 High Q o O c O m O O 0I O -- O O cC O O O O North Target 4 low O East 0 L. w Wall South Target 4 low O South Wall 0 Low East Wall South Wall Figure 6: Thermocouple Placement Shown for East Wall, South Wall and Target Units 2023 Powerwall 3 ANSI/CAN%UL 9540A:2019 Fourth Edition Test Report supplemental Guide 8 Tested Configuration: The initiating unit was placed in the center of the 8' wall opposite the Unit Level Test (cont.) ventilation opening, with target units installed on both sides with 25 mm (1") lateral spacing. All units were 32 mm (1.25") from grade. 2.44 m(8 ft) { i 294.2 mm 25 mm 25 mm 294.2 rnni ro k ! A � Target Target � 3 I Enclosure#1 Enclosure#2 I ; Figure 7: Illustration 5 from Test Report Displaying Initiating and Target Unit Placement Initiating and target units were affixed directly to the wall without the utilization of a mounting bracket; this was done to allow testing to be representative of the worst-case allowable installation configuration. In this installation configuration, and in accordance with manufacturer installation instructions, the BESS enclosure is directly secured to the wall with a single fastener. Installation configuration is noted in the manufacturer installation instructions as ground-mount Powerwall 3 with a Single Fastener, as shown in the following excerpt from the installation instructions. j Ground-mount Ground-or Wall- I Ground-mount Ground-mount Powerwall 3 with mount Powerwall 3 Powerwall 3 on Poured Powerwall 3 on Poured ; a Single Fastener 'with Wall Bracket Concrete I Concrete with Steel 1(Preferred) Posts 0kf � ; I I 11 _rS j Wall and ; Existing I Existing structural wall Existing structural wall Poured concrete with Foundation structural wall j and existing approved and poured concrete steel posts and existing ',,foundation foundation .4 'approved foundation } Seismic 1AorB 1A, B, C, orD A, B, C, orD I A', B, C, orD Design a Category f 2023 Powerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental Guide 9 Internal Fire Condition: The unit level test begins with the application of heat at a specific Unit Level Test site selected to present the greatest amount of thermal exposure to adjacent cells within the module. This application of heat must result in an internal fire condition in accordance with the module level test previously conducted.This was verified by testing staff using temperature data recorded during initiation of the event, compared against the cell surface temperature at thermal runaway during the cell level test. This temperature was determined to be 1880C in accordance with 7.3.1.9 of the test standard - see page 37 of the test report. Thermal Runaway was induced consistent with the methodology determined in the module level test. Internal fire conditions were confirmed using thermocouples placed inside the initiating unit to monitor cell level surface temperatures. Thermal runaway was confirmed in the target and initiation cells with no further propagation to other cells within the module. Cell Cell26 Cell Cell25 Cell Cell24 Cell Cell23 Cells 1 Cell 22 Cell Cell 21 Cell 7 Target C«eJl, Cell 8 Note: Thel heater was placed Cell 9 Cell 18 between Cell 19 and Cell 20 Cell 10 Cell 17 Cell 11 Cell 16 Figure 8: Illustration 3 from the Cell 12 Cell 15 Test Report Displays Target and Initiator Cell Locations Relative Cell 13 Cell 14 to the Greater Module • 0 0T3 • 0 Ta • 0 • • t5 • OWM B • • [1 -'0 • I I Bottom Heater • T2 1 • • • 0 0I • I • • I offlo • • • 0 • • Propagating Thermal Runaway • I I • • I I • 0 - I • • I Limited to Cells Boxed in Red Figure 9: Illustration 4 from the Test Report Displays Film Heater Placement and Internal Thermocouple Placement that was Utilized to Confirm an Internal Fire Condition 2023 Power4wall 3 ANSI/CAN/UL 9540A;2019 Fourth Edition Test Report Supplemental Guide 10 Unit Level Test. Beginning on page 13 of the test report, all required information to Test Results be included in the unit level report is provided in long form. The unit level performance criteria table begins on page 16 of the report, with the applicable performance criteria for residential installations beginning on page 17. Unit level performance criteria indicated in Table 9.1 of the test report provides a basis for the approval of the test report through satisfactory conformance to all required unit level performance characteristics. A summary of key sections of the performance criteria are provided below. Cheesecloth DUT was wrapped in cheesecloth during entirety of test procedure. No flaming or charring was observed outside of the unit, and the cheesecloth indicator was not burned or charred. The cheesecloth is noted "as is after the test" on page 23 of the test report. Cheesecloth is frequently used as a fire indicator in regulatory and safety testing to assess fire hazards during abnormal operations; similarly, the cheesecloth is required by the ANSI/CAN/UL 9540A test standard to ensure an internal fire is contained by the unit level enclosure. 4 1 Figure 10: Photo 6 from the Test Report Displaying "Cheesecloth as is After the Test" 2023 Powerwali 3 ANS!/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental Guide 11 Unit Level Test: Test Results (cont.) Target Units: Target unit module surface temperatures did not exceed the Maximum Temperature temperature at which cell venting occurs (174°C as determined in accordance with Section 7.3.1.8 of the test standard). • Maximum instantaneous temperature recorded by thermocouples was 173.4°C for < is • Temperature spike remains below cell vent temperatures but is attributed to a momentary thermocouple short as denoted in the relevant sections of Table 9.1 in the test report • Adjacent thermocouples do not experience similar and spontaneous temperature spikes as seen in Illustration 12 on page 30 of the test report • Maximum sustained target unit temperatures were ascertained using a rolling 5 second average. Maximum sustained target unit temperature is 96.3°C as indicated in test report Instrumented Walls: • UL 9540A requires BESS intended for installation on Maximum Temperature combustible substrates to limit surface temperature on wall surfaces, to not exceed 97°C temperature rise above ambient • Maximum recorded wall temperature: 54.6°C (39.1°C rise over ambient) • Recorded wall surface temperature rise over ambient is well below allowed maxima noted per Section 9.2.15 of the test standard and does not present a hazard of igniting combustible substrates upon which the BESS is mounted Deflagration/Explosion Hazards • No flying debris or explosive discharge of gases were observed during testing • No sparks, electrical arcing, or other electrical events were observed during testing • No damage was observed to the initiating BESS unit or target BESS units • No damage was observed to the adjacent walls or ceiling of the NFPA 286 standard fire test room For any questions on the test report or this supplemental guide, please email codecomplianceCabtesla.com. 2023 aowerwall 3 ANSI/CAN/UL 9540A:2019 Fourth Edition Test Report Supplemental Guide 12 Test Report issued under the responsibility of: Intertek Total Quality.Assured. TEST REPORT ANSI/CAN/UL 9540A:2019 Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems Report Reference No...................... : 105193075CRT-001 Tested by(name+signature)......... : Mukund Rana Approved by(name+signature).... Dipesh Patel a1 Date of issue................................... : Jan-12-2023 Revision date.................................. : May-12-2023 Pages.......................................: 39 Testing Laboratory.......................... : Intertek Testing Services NA, Inc. Address...........................................: 3933 US Route 11,Cortland, NY 13045, USA Testing location/procedure............ : 9.1 to 9.8 Testing location/address................ : 1. ESRG-9300 OH-66 Piqua OH 45356 2 Applicant's name ............................ : Tesla, Inc. Address...........................................: 3500 Deer Creek Road Palo Alto, CA 94304 USA Test specification: Standard ......................................... : ANSI/CAN/UL 9540A:2019 +UL CRD`s Test procedure................................ : N/A Non-standard test method...........: N/A Test Report Form No...................... : ANSI/CAN/UL 9540A Test Report Form(s)Originator...... : Intertek MasterTRF..................................... : N/A Test item description....................... : Energy Storage system Trade Mark...................................... : TESLA Manufacturer................................... : Tesla, Inc. Model/Type reference..................... : Powerwall 3(1707000-followed by two numbers;followed by-; followed by one letter.) Ratings............................................ : Refer Illustrations A. List of Attachments(as needed): • None TRF No.ANSI/CAN/UL 9540A Lntertek Total Quality.Assured. Page 2 of 39 Report No.: 105193075CRT-001 Summary of testing Tests performed(name of test and test clause): Testing location: ESRG-9300 OH-66 Piqua OH 45356 ❑ Cell level testing ❑ Module level testing ® Unit level testing ❑ Installation level testing TRF No.ANSI/CAN/UL 9540A ntertek Total Quality.Assured. Page 3 of 39 Report No.: 105193075CRT-001 Copy of markinq plate: ILLUSTRATION A: Rating Label of Powerwall 3 TESLA POWERWALL ENERGY STORAGE SYSTEM GRID SUPPORT UTILITY ORCODE INTERACTIVE&STANDALONE INVERTER TESLA PART NO.1707000-XX-Y SN:XXXXXXXXXX Photovoltaic(PV)&Battery Energy Storage System(BESS)Power Conversion Equipment Nominal 3attery Energy 13.5 Wkv Battery Type Won Protective Class Class I Enclosure Type Type 311 Operating Temperature Range -20°C o 50T De-rated Temperature Ranges 40°C to 50°C PV Inverter Topology Non-Isolated BESS Inverter Topology Isolated Was 130 kg Photovoltaic(PV)&Battery Energy Storage System(BESS)Specifications Nominal Grid Voltage Input 8 Output 240 V(AC) Grid Voltage Range 211 V-264 V(AC) Phase 240 V(AC):2VJ+N+PE BESS Max Supply Fault Current 10 kA(AC) Max Continuous Ouput Current ❑48 A(AC) ❑32 A(AC) ❑40 A(AC) ❑24 A(AC) BESS Max Continuous Input Current 20,a A(AC) Frequency 60 Hz Max Continuous Output Puwar ❑11.5 kVA ❑7.6 WA ❑9.6WA ❑5.7WA BESS Max Continuous Input Pmver 5 WA Paver Factor -1 to+1 PV Ooeragng DC Input Voltage Range W-550 V(DC) PV Operating DC`1PPT Voltage Range 150-480 V(DC) PV Max System Voltage 600 V(DC) PV Max Input Current 13 A(DC) PV DC Arc Fault Protection Type 1 Conforms to UL Sid 9540,UL Std 1741,UL Std 1973,UL Std 1699B Contains FCC ID 2AEM-1755080, XNIR201910805M3 The maximum operating current of this system may be controlled electronically.Refer to manufacturers instructions for more information. TRF No.ANSI/CAN/UL 9540A ntertek Total Quality.Assured, Page 4 of 39 Report No.: 105193075CRT-001 Test item particular.................................................: Energy Storage System(ESS) Equipment mobility....................................................: ® stationary ❑ mobile ❑ portable Installation method ...................................................: ®floor ®wall-mount ❑ rooftop/open garage Installation location ...................................................: ®"residential ❑ non-residential Enviromental category...............................................: ® outdoor ❑ indoor ® indoor conditional unconditional Connection to the mains............................................: ® permanent connection ❑direct plug-in ❑ pluggable equipment ❑for building-in Mass of equipment(kg or lb).....................................: Apprx 130 KG Dimension of equipment(mm or cm or inch)............: 1105mm tall x 609mm wide x 193 mm thick Pollution degree ........................................................: ❑ PD1 ❑ PD2 ® PD3 IP protection class or NEMA rating............................: Type 3R Possible test case verdicts: -test case does not apply to the test object.................: N/A -test object was not evaluated for the requirement.....: N/E -test object does meet the requirement.......................: Pass(P) -test object does not meet the requirement................: Fail(F) -test object reaches the specified condition(s)/info...: Yes or No -test object setup completed as specified.................: C Testing: Date of receipt of test items..........................................: Nov-15-2022 Date(s)of performance of tests....................................: Nov-17-2022 General remarks: "(see Attachment#)"refers to additional information appended to the report. "(see appended table)"refers to a table appended to the report. The tests results presented in this report relate only to the object tested. This report shall not be reproduced except in full without the written approval of the testing laboratory. List of test equipment must be kept on file and available for review. Additional test data and/or information provided in the attachments to this report. Throughout this report a❑ comma/® point is used as the decimal separator. Determination of the test results includes consideration of measurement uncertainty from the test equipment and methods. TRF No.ANSI/CAN/UL 9540A tntertek Total Quality.Assured. Page 5 of 39 Report No.: 105193075CRT-001 ANSI/CAN/UL 9540A Clause Requirement—Test Result-Remark Verdict 5 Construction—General 5.1 Cell -- 5.1.1 The cell information associated with the BESS, including: • Cell chemistry(e.g. NMC, LFP); Lithium Iron Phosphate/Graphite - • the physical format of the cell; Prismatic - rismatic/cylindrical/ ouch • the cell electrical rating in capacity and nominal 3.22V, 172.5Ah voltage; Dimension:62.8±0.5 mm by - • the overall dimensions of the cell, and weight. 281.2±0.5 mm by 86.8±0.5 mm Weight: 3186±40 g. 5.1.2 The cells associated with the BESS comply with UL(MH62898) UL 1973, Yes ANSI/CAN/UL 1973 or not. 5.1.3 Further details included in the cell level test report. UL is 4790311374 - 5.2 Module -- 5.2.1 The modules information associated with the BESS, include: • the generic enclosure material; 1 Module= Unit. Metallicenclosure the general layout of the module contents; 2 rows with 13 cells and all cells • - are in series. Refer Illustration 1. • the electrical configuration of the cells in the 2651 P - modules and the modules in the BESS. 5 2 2 The modules associated with the BESS comply with Refer to TUV Report Yes UL 1973 or not. CN22O35O001. 5.2.3 Further details included in the module level test report. TUV S Report C #64.280.23.60130.01 5.3 Battery energy storage system unit -- 5.3.1 The BESS unit info, include: • the units comply with UL 9540 or not; BESS comply to UL 9540. C Manufacturer:TeslaModel - number: Powerwall 3(1707000- • the manufacturer and model number; followed by two numbers; followed by-;followed by one letter.) 11.5KW,83.72 Nominal DC • electrical ratings; Voltage; Rated capacity: 172.5AH • energy capacity of all BESS. 13.5KWH - 5.3.2 For BESS units,which UL 9540 compliance cannot be determined, to include: N/A • the number of modules in the BESS; BESS complies UL9540. N/A • electrical configuration of the module; N/A • physical layout of the modules in the BESS; N/A • battery management system(BMS); and N/A TRF No.ANSI/CAN/UL 9540A okertek Total Quality_Assured. Page 6 of 39 Report No.: 105193075CRT-001 ANSI/CAN/UL 9540A 'Clause Requirement—Test Result-Remark Verdict N/A • other major components of the BESS; 1105mm tall x 609mm wide x • the BESS enclosure overall dimensions and 193mm thick. _ generic material; Material: Cast Aluminumand It has Glass door. • battery system(s)may be tested as representative of the BESS; battery system(s)is not used. N/A • battery system complies with UL 1973 or not. Yes Any fire detection and suppression systems that are an 5.3.3 integral part of the BESS. No 5.3.4 Further details included in the unit level and if (refer to 9.7,) C applicable, installation level test reports. 5.4 Flow Batteries -- 5.4.1 For flow batteries,to include the following info: • the chemistry; EUT does not have a flow battery. N/A • a generic description of the electrolyte(s); N/A • the overall dimensions of the individual stack; N/A • the electrical rating in capacity and nominal voltage N/A of the cell stack. And the Information of the complete flow battery system: • the manufacturer's name and model number of the N/A system; • the electrical rating in volts and rated storage N/A capacity in Ah or Wh; • the number of cells and stacks in the system; N/A • the maximum volume of electrolyte(s)for the N/A system. 5.4.2 The flow battery system complies with UL 1973 or not. N/A 5.4.3 Further details included in the flow battery thermal N/A runaway determination level test report. 6 Performance—General The tests in this standard are extreme abuse 6.1 conditions conducted on electrochemical energy C storage devices,which may result in various kind of hazards. 6.2 At the conclusion of testing, samples discharged in C accordance with the manufacturer'specifications. All samples disposed of in accordance with local ESRG disposed the sample as Yes regulations. per local guidelines. TRF No.ANSI/CAN/UL 9540A ntertek Total Quality.Assured. Page 7 of 39 Report No.: 105193075CRT-001 9 Unit Level 9.1 Sample and test configuration -- Unit was tested with manufacturer's instructions. Combined testing scenario representative of: -indoor floor mounted residential The unit level test shall be conducted with BESS units use BESS 9.1.1 installed as described in the manufacturer's -outdoor ground mounted C instructions and this section. residential use BESS -outdoor wall mounted residential use BESS -Indoor wall mounted residential use BESS Refer to Photo 3 and 5. Refer to Illustrations 4. The unit level test requires one initiating BESS unit Initiating Unit is in Center and 9.1.2 and target adjacent BESS units representative of an Target Units are installed on left C installation. and Right side. Refer to Illustrations 4. Tests conducted for indoor floor mounted installations Indoor duty was tested to for residential BESS may be considered representative represent both cases. Refer to C of both indoor floor mounted and outdoor ground mounted installations. photo 5. Exception:Testing can be conducted outdoors for N/A outdoor only installations with controlled environment. Depending upon the configuration and design of the BESS (e.g.the BESS is composed of multiple 9.1.3 separate parts within separate enclosures),this testing Actual unit is used in testing. N/A to determine fire characterization can be done at the battery system level. The initiating BESS unit shall contain components 9.1.4 representative of a BESS unit in a complete Actual unit is used in testing. C installation. Combustible components that interconnect the initiating and target BESS units shall be included. Target BESS units shall include the outer cabinet, Target units were used with racking, module enclosures, and components that dummy cells in module enclosure. 9.1.5 C retain cells components.The target BESS unit module Refer to Photo 3 and Refer to enclosures do not need to contain cells. Illustrations 4. Total rest time exceeded 8 hours but within 24 hour timeline. 100% SOC and corresponding module voltage confirmed prior to test The initiating BESS unit shall be at the maximum operating state of charge(MOSOC)for conducting the Test conducted on 11/17/2022 9.1.6 tests in this standard.After charging and prior to 1:15:00pm C testing,the initiating BESS shall rest for a maximum Charging start time: 11/16/2022 period of 8 h at room ambient. 3:45:30 PM Charging END time: 11/16/2022 6:29:56 PM Refer Illustration 20. TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 8 of 39 Report No.: 105193075CRT-001 If a BESS unit includes an integral fire suppression system,there is an option of providing this with BESS does not include an 9.1.7 the DUT. If the BESS unit is provided with an optional integral fire suppression system. No integral fire suppression system,the system shall not be provided on the DUT. Electronics and software controls such as the battery BMS and Software does not rely 9.1.8 management system(BMS)in the BESS are not relied on the testing. Yes upon for this testing. This does not include a fire suppression control in accordance with UL 840.that is external to the BESS, No external fire suppression but provided as part of an integral fire suppression controller N/A system per 9.1.7 9.2 Test method—Indoor floor mounted BESS units The Room ambient temperature was controlled. During the test,the test room environment shall be Ambient Temperature(internal 9.2.1 controlled to prevent drafts that may affect test results. Room): 15.5 °C o Yes Relative Humidity:46/o RH Test Date: Nov-17-2022 Refer to Photo 3 and 5. Any access door(s)or panels on the initiating BESS 9.2.2 unit and adjacent target BESS units shall be closed, Refer to Photo 3. Yes latched and locked. 9 2 3 The initiating BESS unit shall be positioned adjacent to Refer to Photo 3. Yes two instrumented wall sections. Instrumented wall sections shall extend not less than 9.2.4 0.49m horizontally beyond the exterior of the target Refer to Photo 3 and 5. C BESS units. Instrumented wall sections shall be at least 0.61 m 9.2.5 taller than the BESS unit height, but not less than Refer to Photo 3 and 5. C 3.66m in height above the bottom surface of the unit. The surface of the instrumented wall sections shall be 16-mm(5/8-in)gypsum wall is 9.2.6 covered with 16-mm(5/8-in)gypsum wall used. C board and painted flat black. Underneath an appropriately The initiating BESS unit shall be centered underneath sized smoke collection 9.2.7 an appropriately sized smoke collection hood of an / hood of an oxygen consumption C oxygen consumption calorimeter. calorimeter. The light transmission in the calorimeter's exhaust duct The light transmission in the 9.2.8 shall be measured for the duration of the test, and the calorimeter's exhaust duct is measured for the duration of the C smoke release rate shall be calculated. test. Refer to Table 1. No heat release recorded by test The chemical and convective heat release rates shall equipment. It is well below under 9'2'9 be measured for the duration of the test, respectively. measurable range of the test C equipment. The heat release rate measurement system shall be The measurement system was 9.2.10 calibrated using flows of 3.8, 7.6, 11.4 and 15.2 L/min calibrated before the testing. C (1, 2, 3 and 4 gpm)of heptane. The convective heat release rate shall be measured 9.2.11 using a thermopile, a velocity probe, and a Type K C thermocouple, located in the exhaust system of the exhaust duct. TRF No.ANSI/CAN/UL 9540A otertek Total Quality.Assured. Page 9 of 39 Report No.: 105193075CRT-001 The convective heat release rate shall be calculated using the following equation: 9.2.12 353 22 T Refer to 9.2.9 C HRR�=1%1 T J C�dT T. The physical spacing between BESS units(both Refer to Photo 3 and 5. Refer to 9.2.13 initiating and target)and adjacent walls shall be Illustrations 4. C representative of the intended installation. 9.2.14 Separation distances shall be specified by the manufacturer for distance between: Distance from BESS Unit and a) The BESS units and the instrumented wall Instrumented wall section: 0 mm sections; and Refer to Photo 3 and 5. C Refer to Illustrations 4. Distance to adjacent Units.( Right &Left target unit from the b) Adjacent BESS units. Initiating unit):25 mm C Refer Photo 3 and 5. Refer Illustrations 4. Wall surface temperature measurements shall be 9.2.15 collected for BESS intended for installation in C locations with combustible construction. If the intended installation is composed completely of noncombustible construction in which wall assemblies, cables,wiring and any other combustible materials are not to be present in the BESS installation,then the C report should note that the installation shall contain no combustible construction and that surface temperature rises can be deemed not applicable. Wall surface Temperature measurement was as follows. TC Locations on East Walls: 16 Wall surface temperatures shall be measured in TCs are on Wall with 6 inch apart 9.2.16 vertical array(s)at 152-mm (6-in)intervals for the TC locations on South Walls : 16 C full height of the instrumented wall sections. TC are connected from the bottom of the wall with 6 inch part. TC:Thermo couple The thermocouples for measuring the temperature on wall surfaces shall be horizontally positioned in the wall Temperature was measured locations anticipated to receive the greatest thermal using type K,24AWG C exposure from the initiating BESS unit. Thermocouples shall be secured to gypsum surfaces Thermocouples were secured by 9.2.17 by the use of staples placed over the insulated portion staples. C of the wires. The thermocouple tip shall be depressed into the gypsum so as to be flush with the gypsum surface at the point of measurement and held in thermal contact C with the surface at that point by the use of pressure- sensitive paper tape. Heat flux shall be measured with the sensing element of at least two water-cooled 9.2.18 Schmidt-Boelter gauges at the surface of each instrumented wall: N/A a) Both are collinear with the vertical thermocouple Optional as per CRD dated November 12,2019 if N/A array; cheesecloth is used. TRF No.ANSI/CAN/UL 9540A tnkertek Tate Quality.Assured. Page 10 of 39 Report No.: 105193075CRT-001 b) One is positioned at the elevation estimated to Refer 9.2.18.a N/A receive the greatest heat flux due to the thermal runaway of the initiating module; and c) One is positioned at the elevation estimated to Refer 9.2.18.a N/A receive the greatest heat flux during potential propagation of thermal runaway within the initiating BESS unit. Heat flux shall be measured with the sensing element of at least two water-cooled 9.2.19 Schmidt-Boelter gauges at the surface of each adjacent target BESS unit that faces the N/A initiating BESS unit: a) One is positioned at the elevation estimated to Refer 9.2.18.a N/A receive the greatest heat flux due to the thermal runaway of the initiating module within the initiating BESS; and b) One is positioned at the elevation estimated to Refer 9.2.18.a N/A receive the greatest surface heat flux due to the thermal runaway of the initiating BESS. For non-residential use BESS, heat flux be measured Refer 9.2.18.a N/A with the sensing element of at least one water-cooled 9.2.20 Schmidt-Boelter gauge positioned at the mid height of the initiating unit in the center of the accessible means of egress. 9.2.21 Measure the temperature of: • the surface proximate to the cells and between the Refer to Illustration 3. C cells and exposed face of the initiating module; One module= Unit. • Each non-initiating module enclosure within the initiating BESS unit; single module in BESS unitRefer C to Illustrations 4. • convoluted enclosure interior geometries. C 9 2 22 For residential use BESS,the DUT shall be covered Refer to Photo 4. C with a single layer of cheese cloth ignition indicator. An internal fire condition in accordance with the module level test shall be created within a 9.2.23 single module in the initiating BESS unit: C a) The position of the module shall be selected to present the greatest thermal exposure to adjacent One Module= Unit Test. Single C modules, based on the results from the module module in BESS unit level test; and b) The setup(i.e.type,quantity and positioning)of equipment for initiating thermal runaway in the module shall be the same as that used to initiate Refer 8. N/E and propagate thermal runaway within the module level test(Section 8). The composition, velocity and temperature of the 9.2.24 initiating BESS unit vent gases shall be measured C within the calorimeter's exhaust duct as in 8.2.10. The hydrocarbon content of the vent gas shall be Refer to Illustrations 19 and Table C measured using flame ionization detection. 1. Hydrogen gas shall be measured with a palladium- Refer Illustrations to 17 and Table C nickel thin-film solid state sensor. 1. TRF No.ANSI/CAN/UL 9540A otertek Total Quality.Assured. Page 11 of 39 Report No.: 105193075CRT-001 The hydrocarbon components of the vent gas composition may additionally be measured using a Carried forward from cell level 9.2.25 Fourier-Transform Infrared Spectrometer with a N/E minimum resolution of 1 cm-' and a path length of at test. Refer Illustrations B and C. least 2 m, or an equivalent gas analyzer. 9.2.26 The test shall be terminated if: N/A BESS unit only contains 1 module a) Temperatures measured inside each module within Test was concluded when cell the initiating BESS unit return to ambient N/A temperature; temperatures returned below Vent Temperature. b) The fire propagates to adjacent units or to adjacent No fire observed outside of the N/A walls; or initiating unit enclosure No hazardous conditions c) A condition hazardous to test staff or the test observed N/A facility requires mitigation. For residential use systems,the gas collection data shall be compared to the smallest room installation Refer to Table 1. Refer to 9.2.27 specified by the manufacturer to determine if the Illustration 17 and 19. C flammable gas collected exceeds 25% LFL in air. 9.3 Test method—Outdoor ground mounted units -- Refer 9.1.2 Outdoor ground mounted non-residential use BESS Initiating Unit is in Center and 9.3.1 being evaluated for installation in close proximity to Target Units are installed on left C buildings and structures. and Right side. Refer to Illustration 4. If intended for outdoor use only installations,the smoke release rate, the convective and chemical heat release Refer 9.3.1 C rate and content,velocity and temperature of the released vent gases need not be measured. Outdoor ground mounted residential use BESS being 9.3.2 evaluated for installation in close proximity to buildings Refer 9.2.18.a N/E and structures. Heat flux measurements for the accessible means of N/E egress. If intended for outdoor use only installations,the smoke release rate, the convective and chemical heat release Refer 9.3.1 C rate and content, velocity and temperature of the released vent gases need not be measured. Test samples shall be installed as shown in Figure 9.2 9.3.3 in proximity to an instrumented wall section. Refer 9.3.1 C The sample shall be mounted on a support substrate and spaced from the wall in accordance with the minimum separation distances specified by the Refer 9.3.1 C manufacturer. Exception: If the manufacturer requires installation against non-flammable material, the test setup may N/E include manufacturer recommended backing material between the unit and plywood wall. Target BESS shall be installed on each side of the Refer 9.3.1 9.3.4 initiating BESS and keep the min. separation distances Refer Illustration 1 C specified by the manufacturer. TRF No.ANSUCAN/UL 9540A ntertek Total Quality.Assured. Page 12 of 39 Report No.: 105193075CRT-001 9.4 Test Method—Indoor wall mounted units -- Testing of indoor wall mounted BESS shall be in 9.4.1 accordance with Section 9.2, except as modified C in this section. Conduct testing in a standard NFPA 286 fire test room 9.4.2 (12 x 8 x 8-ft)high,with a 2-1/2 x 7-ft high opening. Room size is 12 x 8 x 8-ft C BESS intended for residential installations only may be Instrumented wall section was 9.4.2.1 tested using instrumented wall sections not less than used. C 2.44m (8-ft)in height&width instead of the test room. Refer to Photo 3.Wall mount and floor mount cases are combined The initiating BESS unit shall be positioned on the wall due to single module BESS design 9.4.3 opposite of the door opening,with the center located 4- C ft above the floor, and halfway between adjacent walls. - unit placed at ground level. ESS design and construction supports deviation to combine both cases When residential BESS are tested in accordance with 9.4.2.1, the initiating BESS unit shall be positioned with BESS was placed in the center. 9.4.3.1 the center located 1.22m(4-ft)above the floor, and Refer 9.4.3 C halfway between adjacent walls. Target BESS shall be installed on the wall on each 9.4.4 side of the initiating BESS, at the same height above Refer to Photo 3. C the floor as the initiating BESS. Refer to Illustration 5, 6 and 7 as The wall on which the initiating and target BESS units a result of temperature collection 9.4.5 are mounted shall be instrumented. from the instrumented wall C section. For residential use systems,the gas collection data gathered in 9.2 shall be compared to the smallest room 9.4.6 installation specified by the manufacturer to determine Refer to Table 1. C if the flammable gas collected exceeds 25% LFL in air. 9 4 7 For residential use BESS,the DUT shall be covered Refer to photo 4. C with a single layer of cheese cloth ignition indicator. 9.4.8 When testing BESS for residential only installations, Refer 9.2.9. 9.2.18 and 9.2.19 for the criteria in 9.2.9. 9.2.18 and 9.2.19 may be waived. Information only. 9.5 Test Method—Outdoor wall mounted units -- Testing of outdoor wall mounted BESS shall be in It is combined with Indoor wall 9.5.1 accordance with Section 9.2,except as modified mount location and Indoor test C in this section. data is used in the report section. If intended for outdoor use only wall mount installations,the smoke release rate,the convective and chemical heat release rate; C and the content,velocity and temperature of the released vent gases need not be measured. Test samples shall be mounted on an instrumented Test samples is mounted on an 9.5.2 wall (undersurface of the eave shown in Figure 9.4). instrumented wall C The initiating BESS unit shall be positioned on the 9.5.3 instrumented wall,with its center located 4-ft above the C floor,and halfway between wall edges. TRF No.ANSI/CAN/UL 9540A intertek Tatal Quality.Assured. Page 13 of 39 Report No.: 105193075CRT-001 Target BESS shall be installed on the wall on each side of the initiating BESS, at the same height 9.5.4 above the floor as the initiating BESS and keep the C min. separation distances specified by the manufacturer. The wall on which the initiating and target BESS units Instrumented wall section is used 9.5.5 are mounted shall be instrumented. to mount target units C For residential use BESS,the DUT shall be covered cheesecloth was wrapped on the 9.5.6 with a single layer of cheese cloth ignition indicator. unit. C 9.6 Rooftop and open garage installations -- Testing of BESS intended for non-residential use No Rooftop and open garage 9.6.1 rooftop or open garage installations shall be in installations N/A accordance with 9.2. If intended for rooftop and open garage use only installations,the smoke release rate,the 9.6.2 convective and chemical heat release rate and content, N/A velocity and temperature of the released vent gases need not be measured. 9.7 Unit level test report -- 9 7 1 The report on the unit level testing shall identify the type of installation being tested, as follows: a) Indoor floor mounted non-residential use BESS; No N/A b)Indoor floor mounted residential use BESS; Yes C c)Outdoor ground mounted non-residential use BESS; No N/A d)Outdoor ground mounted residential use BESS; Yes C e) Indoor wall mounted non-residential use BESS; No N/A f) Indoor wall mounted residential use BESS; Yes C g)Outdoor wall mounted non-residential use BESS; No N/A h)Outdoor wall mounted residential use BESS; Yes C i) Rooftop installed non-residential use BESS;or No N/A j)Open garage installed non-residential use BESS. No N/A Testing represents Indoor and If testing is intended to represent more than one Outdoor duty with Wall mount and 9.7.2 installation type, this shall be noted in the report. Floor mount tested together. One C test was used to fill up report for all cases. Refer table 9.1 9.7.3 The report shall include the following, as applicable: Manufacturer:Tesla model number: Powerwall 3 a) Unit manufacturer name and model number(and 1707000 -followed by two C whether UL 9540 compliant); numbers;followed by-; followed by one letter. UL 9540:Yes b) Number of modules in the initiating BESS unit; One C c) The construction of the initiating BESS unit per 5.3; Refer Illustrations 1,2 and 3. C d) Fire protection features/detection/suppression No such feature. No systems within unit; TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 14 of 39 Report No.: 105193075CRT-001 e) Module voltage(s)corresponding to the tested 100%SOC 86.7 VDC prior test. C SOC; f) The thermal runaway initiation method used; Film heaters C g) Location of the initiating module within the BESS Single module design.. See C unit; Illustration. h) Diagram and dimensions of the test setup including mounting location of the initiating and target BESS Refer to Illustration 4. C. units, and the locations of walls, ceilings, and soffits; i) Observation of any flaming outside the initiating No flaming outside the initiating BESS enclosure and the maximum flame BESS enclosure. No extension; j) Chemical and convective heat release rate versus Refer to Table 2. C time data; k) Separation distances from the initiating BESS unit A=0 mm. C=N/A C to target walls(A and C in Figure 9.1); Refer photo 3 and 4. D=25 mm. H=N/A. 1) Separation distances from the initiating BESS unit Refer to Illustration 4 C to target BESS units(D and H in Figure 9.1); . Refer photo 1 and 3. Refer 9.1.2 The maximum wall surface= 54.6 °C(East Wall 1) Maximum wall surface temperature(rolling 5 second average) = 54.5°C(East Wall 1). Refer Illustration 5,6 and 7. m) The maximum wall surface and target BESS temperatures achieved during the test and the Maximum Target BESS C location of the measuring thermocouple; temperatures= 173.4°C,(South Target 3) Maximum Target BESS temperatures (rolling 5 second average) = 96.3°C(South Target 3). Refer Illustration 11, 12 and 13. The maximum ceiling or soffit surface temperatures= 125.2 °C n) The maximum ceiling or soffit surface (Ceiling 1 wall) temperatures achieved during the indoor or maximum ceiling or soffit surface C outdoor wall mounted test and the location of the measuring thermocouple; temperatures (rolling 5 second average) = 121.0°C Refer Illustration 8. o) The maximum incident heat flux on target wall N/A surfaces and target BESS units; p) The maximum incident heat flux on target ceiling or soffit surfaces achieved during the indoor or Refer 9.2.18 and 9.2.19 N/A outdoor wall mounted test; q) Gas generation and composition data Refer to table 2. Refer to C Illustration 15, 16, 17, 18 and 19. r) Peak smoke release rate and total smoke release Refer to table 2. Refer to C data; Illustration 17. TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 15 of 39 Report No.: 105193075CRT-001 s) Indication of the activation of integral fire protection No such fire protection in the systems and if activated the time into the test at BESS. N/A which activation occurred; t) Observation of flying debris or explosive discharge No flying debris or explosive No of gases; discharge of gases. u) Observation of re-ignition(s)from thermal runaway No Observation of re-ignition No events; fromThermal run away event. v) Observation(s)of sparks, electrical arcs, or other No spark or arcs No electrical events; w) Observations of the damage to: No 1)The initiating BESS unit; Refer to photo 6. No damage to No initiating unit. 2)Target BESS units; Refer to photo 6. No damage to No target unit. 3)Adjacent walls, ceilings, or soffits; and Refer photo 6. No damage to any No adjacent walls and ceilings. x) Photos and video of the test. Photos and video are taken. Yes 9.8 Performance at unit level testing -- Installation level testing in Section 10 is not required if Refer to table 9.1, Residential 9.8.1 the performance conditions outlined in Table 9.1 are installations. P met during the unit level test. TRF No.ANSI/CAN/UL 9540A Lntertek Total Quality.Assured. Page 16 of 39 Report No.: 105193075CRT-001 Table 9.1 Unit Level Performance Criteria 1. Non-Residential Installations Result a) Flaming outside the initiating BESS unit is not observed; N/A b) Surface temperatures of modules within the target BESS units adjacent to the N/A initiating BESS unit do not exceed the temperature at which thermally initiated cell venting occurs, as determined in 7.3.1.8; (1) c) For BESS units intended for installation in locations with combustible N/A Indoor constructions,surface temperature measurements on wall surfaces do not Floor exceed 97°C of temperature rise above ambient per 9.2.15; Mounted d) Explosion hazards are not observed, including deflagration, detonation or N/A accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and e) Heat flux in the center of the accessible means of egress shall not exceed 1.3 N/A kW/m2. a) If flaming outside of the unit is observed,separation distances to exposures N/A shall be determined by greatest flame extension observed during test. b) Surface temperatures of modules within the target BESS units adjacent to the N/A initiating BESS unit do not exceed the temperature at which thermally initiated cell venting occurs, as determined in 7.3.1.8; (2) c) For BESS units intended for installation near exposures,surface temperature N/A Outdoor measurements on wall surfaces do not exceed 97°C of temperature rise above Ground ambient per 9.2.15; Mouted d) Explosion hazards are not observed, including deflagration, detonation or N/A accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and e) Heat flux in the center of the accessible means of egress shall not exceed 1.3 N/A kW/m2. a) Flaming outside the initiating BESS unit is not observed; N/A b) Surface temperatures of modules within the target BESS units adjacent to the N/A initiating BESS unit do not exceed the temperature at which thermally initiated cell venting occurs,as determined in 7.3.1.8; (3) c) For BESS units intended for installation in locations with combustible N/A Indoor Wall construction, surface temperature measurements on wall surfaces do not Mounted exceed 97°C of temperature rise above ambient per 9.2.15; d) Explosion hazards are not observed, including deflagration,detonation or N/A accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and e) Heat flux in the center of the accessible means of egress shall not exceed 1.3 N/A kW/mz. a) Flaming outside the initiating BESS unit is not observed; N/A (4) b) Surface temperatures of modules within the target BESS units adjacent to the N/A initiating BESS unit do not exceed the temperature at which thermally initiated Outdoor Wall cell venting occurs, as determined in 7.3.1.8; Mounted c) For BESS units intended for installation on walls with combustible construction, N/A surface temperature measurements on wall surfaces do not exceed 97°C of temperature rise above ambient per 9.2.15; TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 17 of 39 Report No.: 105193075CRT-001 d) Explosion hazards are not observed, including deflagration,detonation or N/A accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and e) Heat flux in the center of the accessible means of egress shall not exceed 1.3 N/A kW/m2. a) If flaming outside the unit is observed, separation distances to exposures shall N/A be determined by greatest flame extension observed during test; b) Surface temperatures of modules within the target BESS units adjacent to the N/A initiating BESS unit do not exceed the temperature at which thermally initiated cell venting occurs, as determined in 7.3.1.8; (5) c) For BESS units intended for installation in locations with combustible N/A Rooftop construction,surface temperature measurements on wall surfaces do not and Open exceed 97°C of temperature rise above ambient per 9.2.15; Garages d) Explosion hazards are not observed, including deflagration, detonation or N/A accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and e) Heat flux in the center of the accessible means of egress shall not exceed 1.3 N/A kW/mz. 2. Residential Installations Result a) Flaming outside the initiating BESS unit is not observed as demonstrated by no P flaming or charring of the cheesecloth indicator; Remark: No Flaming outside the initiating BESS unit is observed. b) Surface temperatures of modules within the target BESS units adjacent to the P initiating BESS unit do not exceed the temperature at which thermally initiated cell venting occurs, as determined in 7.3.1.8; Remark: Average cell surface temperature at gas venting,°C: 174. Average surface temperature at thermal runaway, °C: 188 Maximum Target BESS temperatures(rolling 5 second average) °C = 96.3 (South Target 3). (1) Indoor (Note:Thermocouple reports max observed temperature as 173.4°C for <1s. Floor Not sustained and spontaneous <1 s temperature spike attributed to Mounted momentary thermocouple short,temperature spike not supported by temperature measurements on proximally located thermocouples. Refer Illustration 11, 12 and 13) c) For BESS units intended for installation in locations with combustible P construction,surface temperature measurements on wall surfaces do not exceed 97°C of temperature rise above ambient per 9.2.15; Remark: Refer 9.7.3.m and 9.7.3.n. d) Explosion hazards are not observed, including deflagration, detonation or P accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and Remark: Nc-Explosion hazards or deflagration,detonation or accumulation TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 18 of 39 Report No.: 105193075CRT-001 e) The concentration of flammable gas does not exceed 25%LFL in air for the P smallest specified room installation size. Remark: Data is represented from cell level test. Room size is not specified in the cell level. The exhaust gas LFL is 7.05%vol(at Room ambient Temperature);6.05%vol (at vent Temperature);This data is from Single cell level test. a) If flaming outside the unit is observed,separation distances to exposures shall P be determined by greatest flame extension observed during test. Remark: No Flaming outside the initiating BESS unit is observed. b) Surface temperatures of modules within the target BESS units adjacent to the P initiating BESS unit do not exceed the temperature at which thermally initiated cell venting occurs,as determined in 7.3.1.8; Remark: Average cell surface temperature at gas venting, °C: 174. Average surface temperature at thermal runaway, °C: 188Maximum target BESS temperature(rolling 5 second average), °C: Maximum Target BESS temperatures (rolling 5 second average) °C = 96.3 (South Target 3). (Note:Thermocouple reports max observed temperature as 173.4 °C for <1s. Not sustained and spontaneous <1 s temperature spike attributed to (2) momentary thermocouple short,temperature spike not supported by Outdoor temperature measurements on proximally located thermocouples. Refer Ground Illustration 11, 12 and 13) Mounted c) For BESS units intended for near exposures,surface temperature P measurements on wall surfaces do not exceed 97°C of temperature rise above ambient per 9.2.15; Remark: Refer 9.7.3.m and 9.7.3.n. d) Explosion hazards are not observed, including deflagration,detonation or P accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and Remark: No Explosion hazards or deflagration,detonation or accumulation e) Heat flux in the center of the accessible means of egress shall not exceed 1.3 N/A kW/mz. Remark: Refer 9.2.18 and 9.2.19 a) Flaming outside the initiating BESS unit is not observed as demonstrated by no P flaming or charring of the cheesecloth indicator; Remark: No Flaming outside the initiating BESS unit is observed. TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 19 of 39 Report No.: 105193075CRT-001 (3) b) Surface temperatures of modules within the target BESS units adjacent to the P Indoor Wall initiating BESS unit do not exceed the temperature at which thermally initiated Mounted cell venting occurs,as determined in 7.3.1.8; Remark: Average cell surface temperature at gas venting,°C: 174. Average surface temperature at thermal runaway, °C: 188 Maximum Target BESS temperatures(rolling 5 second average) °C = 96.3 (South Target 3). (Note:Thermocouple reports max observed temperature as 173.4°C for <1s. Not sustained and spontaneous <1 s temperature spike attributed to momentary thermocouple short,temperature spike not supported by temperature measurements on proximally located thermocouples. Refer Illustration 11, 12 and 13) c) For BESS units intended for installation in locations with combustible P construction,surface temperature measurements on wall surfaces do not exceed 97°C of temperature rise above ambient per 9.2.15; Remark: Refer 9.7.3.m and 9.7.3.n. d) Explosion hazards are not observed, including deflagration,detonation or P accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases;and Remark: No Explosion hazards or deflagration,detonation or accumulation e) The concentration of flammable gas does not exceed 25%LFL for the smallest P intended room installation size. Remark: Data is represented from cell level test. Room size is not specified in the cell level. The exhaust gas LFL is 7.05%vol(at Room ambient Temperature);6.05%vol (at vent Temperature);This data is from Single cell level test. a) Flaming outside the initiating BESS unit is not observed as demonstrated by no P flaming or charring of the cheesecloth indicator; Remark: No Flaming outside the initiating BESS unit is observed. b) Surface temperatures of modules within the target BESS units adjacent to the P initiating BESS unit do not exceed the temperature at which thermally initiated cell venting occurs, as determined in 7.3.1.8; Remark: Average cell surface temperature at gas venting, °C: 174. Average surface temperature at thermal runaway, °C: 188 (4) Maximum Target BESS temperatures (rolling 5 second average) °C = 96.3 Outdoor (South Target 3). Wall Mounted (Note:Thermocouple reports max observed temperature as 173.4°C for <1s. Not sustained and spontaneous <1 s temperature spike attributed to momentary thermocouple short,temperature spike not supported by temperature measurements on proximally located thermocouples. Refer Illustration 11, 12 and 13) c) For BESS units intended for installation in locations with combustible P construction,surface temperature measurements on wall surfaces do not exceed 97°C of temperature rise above ambient per 9.2.15;and Remark: Refer 9.7.3.m.and 9.7.3.n. TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 20 of 39 Report No.: 105193075CRT-001 d) Explosion hazards are not observed, including deflagration,detonation or P accumulation(to within the flammability limits in an amount that can cause a deflagration)of battery vent gases. Remark: No Explosion hazards or deflagration,detonation or accumulation Note(s): Unit level testing shows adherence to Table 9.1 performance criteria. Unit level tests demonstrate induced thermal runaway not propagated past target cell TRF No.ANSI/CAN/UL 9540A otef tek Total Quality.Assured. Page 21 of 39 Report No.:,105193075 CRT-001 Photo 1: Cell-CB6H0 a Photo 2:Test Set up-1 n I» Photo 3:Test Set up—Heat Flux Sensors EAST SIDE North outh TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 22 of 39 Report No.: 105193075CRT-001 Photo 4:Cheese cloth wrapped around Initiating Unit 3 .tr F f. if Photo 5:Room used for Testing EAST SIDE dgd I F North _ South TRF No.ANSUCAN/UL 9540A intertek Total Quality.Assured. Page 23 of 39 Report No.: 105193075CRT-001 Photo 6:After Unit Test-Set up Photo.Cheesecloth as is after the test. s TRF No.ANSI/CAN/UL 9540A tntertek Total QuaJity.Assured. Page 24 of 39 Report No.: 105193075CRT-001 ILLUSTRATIONS Illustration 2:Lay out of Cells in the module and Unit. Illustration 3:Cell lay out in the Module(Unit) Cell Cell26 Cell Cell25 Cell Cell24 Cell Cell23 Cells Cell22 Cell 6 Cell 21 Cell 7 Cell 8 Cell 9 Cell 18 Cell 10 Cell 17 Cell 11 Cell 16 Cell 12 Cell 15 Cell 13 Cell 14 Target Cell Note: Heater was placed between Cell 19 and Cell 20. TRF No.ANSI/CAN/UL 9540A tntertek Total Quality.Assured. Page 25 of 39 Report No.: 105193075CRT-001 Illustration 4:TC locations on the Initiating Unit Powerwail 3 UL 9540a Test.Instrumentation T_'s L �a 2 T5 F+1 F6 ERE- m Heate :,,max., Tz T8 �. Illustration 5: Unit Test Set up Installation with Dimensions PW3 placement- indoor wall mount Front view 8 ft 8ft ---' -'"---- ZS 25 mm mmi 291.2 mm H'i H, �'-�; k-* 294.2 mm Target Enclosure Target #1 Enclosure#2 TRF No.ANSI/CAN/UL 9540A otertelk Total Quality.Assured. Page 26 of 39 Report No.: 105193075CRT-001 Illustration 6:Temperature:South Wall-East Wall Temperature South Wall -East Wall 60 -- — --T—_— --- ------- ---� 50 ----- ------..L— --- --- i f I j i I I � i I V 30 m ti' a E z010 - -'— - I I 1 I I I I 0 0 1000 2000 3000 4000 5000 6000 7000 8000 Relative time seconds —South wall 0low —South wall 1 —South wall 2 —South wall 3 —South wall 4 —South wall 5 —South wall 6 —South wall 7 —South wall 8 —South wall 9 —South wall 10 —South wall 11 —South wall 12 —South wall 13 —South wall 14 —South wall 15 high—East Wall 0low —East Wall 1 —East Wall —East Walla ---East Wall --East Wall S —East Wall 6 —East Wall 7 —East Wall —East Wall East Wall 10 East Wall 11 —East Wall 12 ----East Wall 15 high —South wall 0low —South wall 1 —South wall 2 —South wall 3 —South wall 4 —South wall 5 —South wall 6 —South wall 7 —South wall 8 —South wall 9 —South wall 10 —South wall 11 —South wall 12 —South wall 13 —South wall 14 —South wall 15 high—East Wall 0low —East Wall 1 —East Wall —East Wall —East Wall —East Wall 5 —East Wall —East Wall TRF No.ANSI/CAN/UL 9540A Ln to r te k Total Quality.Assured. Page 27 of 39 Report No.: 105193075CRT-001 Illustration 7:Temperature:South Wall Temperature South- Wall 40 I I l i i I j I I I I i 35 — -- -- --- I- — 30 -- I I 1 25 -- U f 1 � { H 15 f ^� 10 I I � � r 0 I 0 1000 2000 3000 4000 5000 6000 7000 8000 Relative time seconds —South wall 0low —South wall 1 —South wall 2 —South wall 3 —South wall 4 —South wall 5 —South wall 6 —South wall 7 —South wall 8 —South wall 9 —South wall 10 —South wall 11 —South wall 12 —South wall 13 —South wall 14 — South wall 15 high—South wall 0 low —South wall 1 —South will 2 —South wall 3 —South wall 4 —South wall 5 —South wall 6 —South wall 7 —South wall 8 —South wall 9 —South wall 10 —South wall 11 —South wall 12 —South wall 13 --- South wall 14 --- South wall 15 high TRF No.ANSI/CAN/UL 9540A intertchk Total Quality.Assured. Page 28 of 39 Report No.: 105193075CRT-001 Illustration 8:Temperature: East Wall Temperature East-Wall 60 ---- I , I j I 50 j I I I i I j I 40 ! V , cc I � V i l- - i 306. d I a j 20 f 1 10 — ------ -- — i 0 i 1 0 1000 2000 3000 4000 5000 6000 7000 8000 Relative time seconds —East Wall 0low —East Wall 1 —East Wall 2 —East Wall —East Wall —East Walls —East Wall —East Wall —East Wall —East Wall —East Wall 10 ----East Wall 11 —East Wall 12 ---East Wall 15 high—South wall 0low —East Wall 0low —East Wall 1 —East Wall 2 —East Wall a —East Wall 4 —East Wall 5 —East Wall —East Wall 7 —East Wall —East Wall -----East Wall 10 --East Wall 11 —East Wall 12 —East Wall 15 high TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 29 of 39 Report No.: 105193075CRT-001 Illustration 9:Temperature:Ceiling i Temperature Ceiling I 140 I I 120 i 100 C I j C) I 0 60 r 40 - I 20 i i I ? � 0 i 0 1000 2000 3000 4000 5000 6000 7000 8000 Relative time(Sec) I € —Ceiling 1 wall —Ceiling 2 Illustration 10: Temperature Initiator Unit with Cell designation Temperature Initiator Unit with Cell designation I 2000 - 1800 — i 1600 l 1400 — -- — ---; - -' ----y I 1200 1000 800 {- 600 ---—. —; --- t------ -- - -----.--� j400 i a i 200 - 0 0 1000 2000 3000 4000 5000 6000 7000 8000 1 —Cell 7-Initiator 1 —Cell 8-Initiator —Cell 23-Initiator 3 —Cell 22-Initiator 4 —Cell 18Initiator 8 —Cell 17 Initiator 9 —Cell 21-Target Cell-Initiator 5 —Cell 20Initiating Cell-Initiator 6 - - - -- - - - - __ . . . , -._--- __ --_--------------- - -- --- - - - - --.. Note:--There---is some- --Bad- -data-recorded---on--cell 22-_from 1077.. to-1201_---Sec.__T,h hermal runaway did no[propagate to cell 22 TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 30 of 39 Report No.: 105193075CRT-001 Illustration 11: Temperature Initiator Unit with Cell designation—Without Cell 22 I Temperature Initiator Unit with Cell designation 500 i I ; 450 400 i I I i I I I 3S0 300 250 - 200 - -- - --r------i --�-- -- I------F---— --- 150 I 100 50 - '— - ----` - — - -- -- 0 I 0 1000 2000 3000 4000 5000 6000 7000 8000 j i-.. 1 � I I I —Cell 7-Initiator 1 —Cell 8-Initiator 2 —Cell 23-Initiator 3 —Cell 18 Initiator 8 —Cell 17 Initiator 9 —Cell 21-Target Cell-Initiator S —Cell 20 Initiating Cell-Initiator 6 —Cell 19 Initiating Cell-Initiator 7 ' Illustration 12:Temperature Target units-North unit and South Unit Target units It North and South 200 I .—.._..___._ .,.. i 180 i 160 j--- ----'------...--- '---' ---- - �' --- -- --_ ----- 140 120 I--'- - - .... - --- -- - - -- - -' -- -- -- -- -- -- -- U100 --' - -- -. - - - --' - -�- - - - - - _. - - .. - -- ----- - 60 i 40 0 1000 2GC0 3000 4000 Sow 6C00 7000 8000 Relative time(sec) —South Targetl high—South Target —South Target3 —South Target4 low —North Targetl high—North Target2 —North Target —North Target4 low I n TRF No.ANSI/CAN/UL 9540A in tca r te k Total Quality.Assured. Page 31 of 39 Report No.: 105193075CRT-001 Illustration 13:Temperature Target unit—North unit Target unit## North 140 120 -- -- -- -------- -----7 I , 100 I 1 30 60 L I 40 -- ---- - -- �---- ------- -- -- , -- - -- - - ---- - - I I 16d --- A 0 - 0 1000 2000 WOO 4000 5000 6000 7000 8000 Relative time(sec) I —North Target Ihigh —NorthTarget2 —NorthTarget3 —North Target4 low Illustration 14:Temperature Target unit-South Unit Target units # South zoo 180 160 140 ' - -.-� 120 --- - -- -- ---- -- ----- ..^------...� () 100 80 - 60 - 40 --- - -- - -- - ZO -- r-�- _ _ 0 0 1000 2000 3000 4000 5000 6000 7000 8000 Relative time(sec) i —South Target 1 high —South Target 2 -South Target 3 —South Target 4 low TRF No.ANSI/CAN/UL 9540A intertchk Total Quality.Assured. Page 32 of 39 Report No.: 105193075CRT-001 Illustration 15:Smoke Release Rate(SRR) SRR (m2/s) c j 0.250000 ( 0.200000 -- — ---�---i -- r--- 0.150000 I ! { 0.100000 - —— — -- ----- I i I i 1 j i 0.050000 0.000000 I 0 1000 2000 3000 4000 5000 6000 7000 i Relativr time(Sec) { i —SRR(m2/s)Clean j TRF No.ANSI/CAN/UL 9540A in to r tcz k Total Quality.Assured. Page 33 of 39 Report No.: 105193075CRT-001 Ilustration 16: CO%Vol CO IBR (% Vol) 0.010000 -----r----- -------�----„ —— - i 0.008000 -- � y I 0.006000 -i _,1- -- ---- - L_ —.___-4 o ? I 1 0.004000 -- _._ ___. f--___ 7 -- 1 0.002000 i 0.000000 0 1000 2000 3000 4000 5000 6000 7000 Relative time(Sec) —CO IBR(%Vol) Illustration 17:CO2 High %Vol CO2 IBR High (%Vol) 0.040000 - - ---- --- I 0.0350000.030000 - ---;--- _--- --- ----r- i I � I 0.025000 -- d, 0.020000 0.015000 0.010000 - 0.005000 ------- --)- I i 0.000000 0 1000 2000 3000 4000 5000 6000 7000 Relative time(Sec) CO2 IBR High(%Val) TRF No.ANSI/CAN/UL 9540A Lntertek Total Quality.Assured. Page 34 of 39 Report No.: 105193075CRT-001 Illustration 18: H2 RKI %Vol H2 RKI IBR (%Vol) 0.200000 0.150000 11, 0.100000I �0.050000 _..__T _ __ I 0.000000 0 1000 2000 3000 4000 5000 6000 7000 Relative time(Sec) H2 RKI IBR(%Vol) Illustration 19:02%Vol 02 (%Vol) 25.000000 - 1 20.000000 -- I ! i 15.000000 10.000000 -- —j----- —— J---- -- i 5.000000 �- I ! I 0.000000 I 0 1000 2000 3000 4000 5000 6000 7000 Relative time(Sec) 02(%Vol) TRF No.ANSI/CAN/UL 9540A htertek Total Quality.Assured. Page 35 of 39 Report No.: 105193075CRT-001 Illustration 20: FID %Vol FID IBR High (% Vol) 0.200000 -----;- ---; --- -----_ --------- i 0.150000 ---— — - -;—--- -- - -- - ---� 3� 0.100000 --- ----- ----'----I---- -----I----- 0.050000 II -- - ---l---- -- -----I ----- 0.000000 0 1000 2000 3000 4000 5000 6000 7000 Relative time(Sec) FID IBR High(%Vol) Illustration 21:Charging Profile of Initiating Unit. --- —_-------------Charging Profile 160 --—f- ,.----i---- ----- --_- 140 ---='— -- - -- 120 ----__---- 100 ---- --- -- + - - - 80 -_t - > 60 -- ---- --- - ---— 40 _. - � I 20 __-- - - --- t --! -- - - i 0 2000 4000 6000 8000 10000 12000 Relative time Sec I ABCVoltage —ABCCurrent —ABCAh TRF No.ANSI/CAN/UL 9540A ntertek Total Quality.Assured. Page 36 of 39 Report No.: 105193075CRT-001 Table is Gas Composition Measured GAS ,Volume measured (Liter). Carbon Dioxide 13.90 Carbon`Monoxide 69.49 Hydrogen (RKI)' 2166.28 Unburned 0.71 Hydrocarbons: Table 2: Heat Release Rate and Smoke Release rate Heat Release Rate (HRR) Smoke Release Rate (SRR) Peak Chemical HRR 0* Peak SRR (m2/sec) 0.22** (KW) Total smoke Released 52.26*** (m2) Notes: (*)The Flaming was not observed during the test. (**)Max Peak is recorded 1097 relative time Sec (***)Totalized smoke release for total duration 6431.5 Sec. TRF No.ANSI/CAN/UL 9540A intertek Total Quality.Assured. Page 37 of 39 Report No.: 105193075CRT-001 APPENDIX A.Cell level data: -Cell thermal runaway methodology(film heaters) -Cell surface temp at venting: 174°C -Cell surface temp at runaway: 188 °C -Cell level UL report- UL#4790311374 B. Module level data: -Cell thermal runaway methodology(Film heaters) - Module heat release rate—33.767KW - Module level Test Report—TUV#64.280.23.60130.01 ILLUSTRATION B: Results of Gas Analysis—Cell level Table Re-normalized Gas Quantification,excluding N2 and O,,and unknown compounds. Item Measure Chemical formula Conc.(%) 1 Carbon Monoxide Co 11.606 2 Carbon Dioxide CO2 25.132 3 Hydrogen H2 50.974 4 Methane CH, 6.384 5 Ethylene C21-14 4.334 6 Acetylene C21-12 O.230 7 Ethane C21-16 0.968 8 Propane CH3CH2CH3 0.042 9 Propylene C3H6 0.173 10 Propadiene(Allene) C31-14 0.000 11 Isobutane CH3CH(CH3)CH3 0.003 12 Butane C41110 0.007 13 Isobutylene C1H3 0.031 14 1-Butene C6H3 0-004 15 trans-2-Butene C1H3 0.008 16 cis-2-Butene C,H3 0.005 17 Pentane CSH12 0.006 18 trans-2-Pentene C5H10 0.000 19 cis-2-Pentene CSH10 0.000 20 1,4-Pentadiene CSH3 0.000 21 Hexane C6H11 0.001 22 1-Hexene C6H11 0.002 23 Benzene C6H6 0.001 24 1-Heptene C711II 0.000 25 Toluene C7H3 0.000 26 Styrene C313 0.000 27 Dimethyl Carbonate C3EW3 0.036 28 Ethyl Methyl Carbonate C6H303 0.006 29 Diethyl Carbonate C51-11003 0.000 Total Measurement result 100.000 Finure 94-rac rmmnnsitinn annlasis rt_- Alt TRF No.ANSI/CAN/UL 9540A intczrtczk Total Quality.Assured. Page 38 of 39 Report No.: 105193075CRT-001 ILLUSTRATION C: Gas composition excluding the constituents with boiling points higher than 60°C—Cell level Cell Gas composition Gas Measured% Carbon Monoxide CO 11.605 Carbon Dioxide CO2 25.132 Hydrogen H2 50.974 Methane CH4 6.384 Acetylene C21-112 O.230 Ethylene C21-14 4.384 Ethane C21-118 0.968 Pro adiene Allene C31-114 N.D Propene C31-116 0.173 Propane C3He 0.042 C4 Total 0.057 C5(Total) 0.006 C6 Total 0.002 1-He tene C7H14 N.D Styrene Celle N.D Benzene CsHs 0.001 Toluene C7He 0.000 Dimeth 1 Carbonate C311-116O3 0.036 Ethyl Methyl Carbonate C411-118O3 0.006 Total - 100 ---------------End of test report--------------- TRF No.ANSI/CAN/UL 9540A tn!tertek Total Quality.Assured. Page 39 of 39 Report No.:,105193075CRT-001 Revision History Revision/ Writer Reviewer Date Change Job Number Initials Initials Rudolph Mukund Updated model from 1.0/ Sporman Rana March 23, 2023 "PW++" or "PW3" to G105375512 "Powerwall 3" Added Rollimng 5 sec data noted in 9.7.m, Mukund Aditya lyer 9.7.n and table 9.1 . 9.0/G105193075 Rana f May-12-2023 Updated some typo. Added Module report number. Removed section 8. -----------END----------- TRF No.ANSI/CAN/UL 9540A l� " ABBREVIATIONS ELECTRICAL NOTES JURISDICTION ®"TES A AMPERE AC ALTERNATING CURRENT BLDG 1. THIS SYSTEM IS GRID—INTERTIED VIA A UL—LISTED ALL WORK TO COMPLY WITH SECTION R327 OF THE PLYWIT ALL LL CODES OF BUILDING CONC CONCRETE DC DIRECT CURRENT POWER—CONDITIONING INVERTER. 2020 RESIDENTIAL CODE OF NYS. NEW YORK STATE&TOWN CODES EGC EQUIPMENT GROUNDING CONDUCTOR (E) 2. A NATIONALLY — RECOGNIZED TESTING APPROVED AS NOTED A REQUI D AND CONDITIONS OF EXISTING EMT ELECTRICAL METALLIC TUBING FSB LABORATORY SHALL LIST ALL EQUIPMENT IN FIRE SET—BACK GALV GALVANIZED GEC GROUNDING COMPLIANCE WITH ART. 110.3. G SOUMOLDTOWNZBA ad— ELECTRODE CONDUCTOR GND GROUND HDG HOT 3. WHERE ALL TERMINALS OF THE DISCONNECTING DATE' —5 � B.P# a g SOUIHOLDTOWNPLANNING DIPPED GALVANIZED I CURRENT Imp CURRENT AT MEANS MAY BE ENERGIZED IN THE OPEN POSITION, BOARD A MAX POWER Isc SHORT CIRCUIT CURRENT kVA A SIGN WILL BE PROVIDED WARNING OF THE BY. SOLUOLD TOWN TRUSTEES KILOVOLT AMPERE kW KILOWATT LBW LOAD HAZARDS PER ART. 690.17. NOTIFY BUILDING DEPARTMENT AT N.Y.$,DEC BEARING WALL MIN MINIMUM (N) NEW NEUT 4. EACH UNGROUNDED CONDUCTOR OF THE 631-765-1802 8AM TO 4PM FOR THE SOUMOLDHPC NEUTRAL NTS NOT TO SCALE OC ON CENTER PL MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY FOLLOWING INSPECTIONS: PROPERTY LINE POI POINT OF INTERCONNECTION PHASE AND SYSTEM PER ART. 210.5. $CHD PV PHOTOVOLTAIC SCH SCHEDULE S STAINLESS 5. CIRCUITS OVER 250V TO GROUND SHALL COMPLY ELECTRICAL FOUNDATION-TWO REQUIRED STEEL STC STANDARD TESTING CONDITIONS TYP WITH ART. 250.97, 250.92(B). INSPECTION REQUIRED FOR POURED CONCRETE TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V 6. DC CONDUCTORS EITHER DO NOT ENTER BUILDING ROUGH-FRAMING&PLUMBING ��OF NEVV Y VOLT Vmp VOLTAGE AT MAX POWER Voc VOLTAGE OR ARE RUN IN METALLIC RACEWAYS OR o AT OPEN CIRCUIT W WATT 3R NEMA 3R, RAIN T IGHT ENCLOSURES TO THE FIRST ACCESSIBLE DC Additional INSULATION C,�P � KAn,,q DISCONNECTING MEANS PER ART. 690.31(E). FINAL-CONSTRUCTION MUST 7. ALL WIRES SHALL BE PROVIDED WITH STRAIN Certification BE COMPLETE FOR C.O. RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY AIIaY Be Required. x UL LISTING. q ALL CONSTRUCTION SHALL MEET THE °C 8. MODULE FRAMES SHALL BE GROUNDED AT THE UL REQUIREMENTS OF THE CODES OF NEW — LISTED LOCATION PROVIDED BY THE YORK STATE. NOT RESPONSIBLE FOR (P 09 ,o MANUFACTURER USING UL LISTED GROUNDING DESIGN OR CONSTRUCTION ERRORS HARDWARE. Rp 101AP 9. MODULE FRAMES, RAIL, AND POSTS SHALL BE BONDED WITH EQUIPMENT GROUND CONDUCTORS. VICINITY MAP INDEX ' Sheet 1 COVER SHEET Sheet 2 SITE PLAN Sheet 3 THREE LINE DIAGRAM a' Sheet 4 POWERWALL MOUNTING DETAIL LICENSE GENE L NOTES Sheet 5 ESS LOCATION DETAIL Cutsheets Attached 1. ALL WORK SHALL COMPLY WITH THE 2020 NYS UNIFORM CODE. 2. ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2017 NATIONAL ELECTRIC CODE. 3. ALL WORK SHALL COMPLY WITH THE 2020 NYS FIRE CODE. MODULE GROUNDING METHOD: WEEB 4. ALL WORK SHALL COMPLY WITH THE 2020 BUILDING CODE OF NYS. " REV BY DATE COMMENTS AHJ: Southold Town 5. ALL WORK SHALL COMPLY WITH THE 2020 REV A NAME DATE COMMENTS RESIDENTIAL CODE OF NYS. 6. ALL WORK SHALL COMPLY WITH THE 2020 UTILITY: PSE&G—Long Island EXISTING BUILDING CODE OF NYS. x k CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: J B-119 3 2 3 6 O O CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT CE USED FOR THE Elias Aliprandis 27 KWH ENERGY STORAGE SYSTEM Pranay Lakkakula BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MouNnNc srsTEM: 5325 Rocky Point Rd SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: East Marion, NY 11939 THE SALE AND USE OF THE RESPECTIVE _-- TESLA EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV: DATE: INVERTER: CC GG PERMISSION OF TESLA INC. 5166727625/ COVER SHEET 1 11/4/2025 ESS UNITS TO BE MOUNTED ON EXTERIOR WALL 3FT FROM DOORS & WINDOWS Q EXTERNAL DISCONNECT SWITCH w � 0 A� O E§ LEGEND O (E) UTILITY SERVICE METER DISTRIBUTION PANEL FAC AC DISCONNECT Front Of House GATEWAY 0 ENERGY STORAGE SYSTEM OF NEvV CO KAN j,y r_ - - LU n � W �ZN v� A�oFES oA WARNING LABELS PROVIDED AT APPLICABLE EQUIPMEN 0 STANDOFF LOCATIONS -- CONDI�IT RUN -- CAT )FENCE d HEAT PRODUCING VENTS ARE RED r'-_-I INTERIOR EQUIPMENT / CONDUIT IS DASHED L-'J SITE PLAN N Scale:1/16" = 1' W E 01, 16' 32' S CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: JB-1193236 00 CUSTOMER: DESCRIPTION: DESIGN; CONTAINED SHALL NOT BE USED FOR THE Elias Aliprandis 27 KWH ENERGY STORAGE SYSTEM Pranay LakkakufaBENEF _ SHALL I OF ANYONE EXCEPT WHOLE INC., NOR MOUNTING s> 5325 Rocky Point Rd ® L SHALL IT BE DISCLOSED IN S'hIOLE OR IN ri PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES East Marion, NY 11939 THE SALE AND USE OF THE RESPECTIVE TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME SHEET: REV: DATE: PERMISSION of TESLA INC. 5166727625 SITE PLAN 2 11/4/2025 A (N) 200A INTERNAL 200A 2P BACKUP GATEWAY LOAD CENTER AC DISCONNECT -91 C 60A P 2 �� 2 D POWERWALL ¢❑ T D POWERVlALL CS ❑ TO 120/240V SINGLE PHASE UTILITY SERVICE - 20DA 2P EXTERNAL DISCONNECT SWITCH (E)LOADS (E)200A DISTRIBUTION PANEL Panel Limit feature for Powerwal► unit(s) to be utilized PCS Controlled Current Setting: (Panel Rating * 0.8) = 160A (200A Busbar) The maximum output current from this system towards the main panel is controlled electronically. Refer to manufacturer's instructions for more information." ,( p f k Ref Qty Description a Size(AWG) Min EGC Conduit Length Imp Vmp.:,r B 1 Eaton BR26OH: 60A/2P 240V BR Thermal Magnetic Circuit Breaker Ref Type Oty (Cu) (AI) (AWG, Cu) (Cu) (AI) (ft) (AAC) (VAC) 1 Tesla #1841000—XX—Y: Back—up Gateway 3.0 NA for PW 1 THWN-2 3 #2/0 #4/0 1,106 2" PVC 2"PVC 2ft — 240 C 1 Disconnect; 60A, 24OVac, Non—Fusible, NEMA 3R: 2P, 2W, Lockable 2 THWN-2 3 #06 #04 #10 PVC Jacketed MC 1"EMT 2ft — 240 1 Ground/Neutral Kit; 60-100A, General Duty(DG) 3 THWN-2 3 #2/0 #4/0 #06 2" PVC 2"PVC 2ft — 240 D 1 Powerwall 3 Expansion Tesia Inc[240V]#18070OD—XX—Y 13.5 kWh 1 Tesio Powerwoll 3[24OV]#1707000—XX—Y 11.5 kW/13.5 kWh 1. CONDUIT RUNS MAY BE CONDENSED DUE TO SITE CONDITIONS AND/OR INSTALLATION EASE. ALL CONDUIT FILL DERATES AND PROPER CALCULATIONS HAVE BEEN COMPLETED PER NEC CHAPTER 9, TABLE 4. 2. SOLAR SHUTDOWN DEVICE TO BE INSTALLED FOR SYSTEM RAPID SHUTDOWN (RSD) IN ACCORDANCE WITH ARTICLE 690 OF THE APPLICABLE NEC. 3. CONDUIT TYPE CAN CHANGE DUE TO SITE CONDITIONS AND WILL FOLLOW THE NEC REQUIREMENTS FOR THAT CONDUIT TYPE. Main Panel Rating (E) 200A Main Breaker (E) 200A Rating General Notes DC Ungrounded Inverters Panel Number Meter Number 80359778 Service Entronce Overhead J 8-119 3 2 3 6 0 0 CUSTOMER: DESCRIPTION: DESIGN: CONFIDENTIAL— THE INFORMATION HEREIN �e NUMBER: Elias i as AI inra n d is CONTAINED SHALL NOT BE USED FOR THE r 27 KWH ENERGY STORAGE SYSTEM Pranay Lakkakula BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM 5325 Rocky Paint Rd SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO THE RECIPIENTS ORGA IZATTIION, EXCEPTIDE N CONNECTION NTH MODULES: East Marion, NY 11939 THE SALE AND USE OF THE RESPECTIVE TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 51 66727625 THREE LINE DIAGRAM 3 11/4/2025 POWERWALL FASTENER SCHEDULE' POWERWALL INSTALLATION INFORMATION. FASTENERS PER WALL TYPE MODEL DIAMETER EMBEDMENT CORNER ESR UNISIRUT REQUIRED? WOOD S!D W000 SCREIV 3S'D 2V i HA YES® t�J 1. POWERWALLS TO BE INSTALLED PER FASTENER SCHEDULE BASED ON WALL TYPE CONCRETE OR CWU CONCRETE SCREFY Yy'G U4' 2� NA NA ANDSITE SPECIFIC CONDITIONS. CONCRETE SIMSPOH TIIEN HO .3•a �a• � �'—i,306(CONC44U� H4 OR 2. DO NOT MOUNT BELOW OR ABOVE WINDOWS OF THE SAME STORY. =CRETE HU,KH tZ •m , z� MR-3027(CONCRETE) OR%AD MR-3056(CMU) 3. IF LOCATION NEEDS TO BE CHANGED, PLEASE CONTACT DESIGN TEAM. SRR= YJLTI MIX CONN6 r" i NA m 4. ANY UNUSUAL FRAMING NEAR THE POWERWALL THAT MAY COMPROMISE THE WALL GRICK HIf MH SLEEVE A10 v' , ESR-4143(Bm) NN STRUCTURAL INTEGRITY SHALL BE RELAYED TO THE DESIGN TEAM PRIOR TO INSTALL. COL STEEL SHEET AMALSCPcm 110 YES ❑ hro 5. WHEN INSTALLING POWERWALL+ THE INVERTER I S A SINGLE UNIT AND CANNOT B E 1. INSTALLER TO CHOOSE FASTENER BASED ON FIELD CONDITIONS, WALL TYPE, AND EASE OF INSTALL 2. 1 CONCRETE & CMU NON-ESR FASTENER CAN BE USED WHEN UNIT(S) ARE MOUNTED ON THE GROUND AND SEISMIC SS (SPA STACKED. WHEN INSTALLING A STACKED ARRANGMENT ONLY ONE POWERWALL+ AND AT SHORT PERIOD) IS AT OR BELOW S, = 1.25. � 3. 1 CONCRETE & CMU ESR FASTENER CAN BE USED WHEN UNIT(S) ARE MOUNTED ON THE GROUND AND SEISMIC SS (SRA AT ONE ADDITIONAL POWERWALL CAN BE INSTALLED. THE LARGEST STACKING SHORT PERIOD) IS AT OR BELOW SS = 2.5 AND REGIONAL WIND SPEED (3-SECOND GUST) IS AT OR BELOW 17OMPH 4. COLD FORMED STEEL MINIMUM 25 GAUGE REQUIRES 3 FASTENERS PER CORNER. BUT 1 FASTENER PER CORNER CAN BE USED CONFIGURATIONS ALLOWED BY THE MOUNTING BRACKETS ARE 3 POWERWALL UNITS WHEN STEEL STUDS ARE 8 GAUGE OR THICKER OR 1 POWERWALL+ AND 1 POWERWALL UNIT WHEN BOX IS CHECKED D{VERSITECH PAD ACP24362 IS APPROVED FOR A SINGLE OUTDOOR POWERWALL GROUND MOUNT AND DIVERSITECH PAD ACP36362 IS APPROVED FOR UP TO 2 STACKED USING A POWERWALL+ AND A POVIERWALL UNIT OR 2 POWERWALL UNITS ,1 of: NEM/ �'<Q' KA/Vjj REFER TO FASTENER SCHEDULE POFSiRNJALL UNIT FOR NUM PEERRR��FARS7ENERS WALL EXAMPLE ff r = `r►� � ONE FASTENER i IN ANY HOLE m LLJ (V PER CORNER I EXAMPLE 100 Og 4 IN ANY HOLE ERS o oS PER CORNER FASTENER TO WALL PER FASTENER SCHEDULE PGAVERWALL+ WALL BRACKET + (N)POWERWALL BRACKET, POWERWALL UNIT NOT SHOWN FOR CLARITY e + r WALL ATTACHMENT: WALL MOUNT SIDE VIEW ONE POWERWALL NTS ATTACHMENT: FRONT VIEW POWERWALL NTS J B-119 3 2 3 6 00 C CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: USTOMER: DESCRIPTION: DESIGN: Elias I C7 S AI I r a n d I S CONTAINED SHALL NOT BE USED FOR THE p 27 KWH ENERGY STORAGE SYSTEM Pranay Lakkakula BENEFIT OF ANYONE EXCEPT TESLA INC., NOR alouNnNc SYSTEM: 5325 Rocky Point Rd - rl SHALL IT BE DISCLOSED IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES East Marion, NY 11939 THE SALE AND USE OF THE RESPECTIVE TESLA EQUIPMENT, WITHOUT THE WRITTEN INVERTER PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 5166727625 POWERWALL MOUNTING DETAIL 4 11/4/2025 EQUIPMENT IS NOT TO SCALE, FOR ILLUSTRATIVE PURPOSES ONLY. GATEWAY AC DISCONNECT POWERWALL POWERWALL 77 5,7 � ', '°R ,...,....mac„--2escww.�+•r.u+ta-..� l �r 7 t f �-' 1�.,..-.....�...�""""'°•r,.. M° irk d ,fit 1 '.,"�f a."^w'�„'m -� mo•� ..+ .x'� :', rr.4 �w.ra. ;k.�.x»..... „M gem, : � w-�..�....�'aA.'".n'°` a�•.-s.- !..�, '"",� c m� .,,a, x Se�...�4. ,: ,_, ---+✓-ems.-,;�'- �..._... i _i w'•-.,u,-°', -:...:n. ,r>...�."`,�� z77. 71 mo-o"�v'sm'aa'++i+�•z+.e�>.�ivmr.'a.,ax �G> _., kv NW 'C`t�+ env'-.c-rvz v�Lmv.+mcrAbe.LEeil 1�� •ylt •v'F9�As -.� �bvPMrtv^r+rl * ¢+v")'`n...rv� -� �e'^� k "E^' Am , ,... _�„ .+n.,.:. ,rt m..�,e.*G.+• �*.v }>�,x w.� �s � zw-u�{� t r, x f 73 to � t i v .,a-z*�.w -�.«.^a^,.-'v' w"•�-"" "ar'sat�"�5` �. �, y'�'" � � ,yK a'A}�H f2 ^t 'v'^ � �� �� v�.ehM�^.✓' �� J Si1+Y 5� irnT -s5whl �My -yr�w.r 4xMK - FS j T P� �v CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: J B-119 3 2 3 6 O O CUSTOMER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT E USED FOR THE Elias Aliprandis 27 KWH ENERGY STORAGE SYSTEM Pranay Lakkakula SHALLIT BE DISCLOSED IN WHOLE OR IN -� BENEFIT OF ANYONE EXCEPT TESLA INC., NOR MOUNTING SYSTEM: 5325 Rocky Point Rd SHALL PART TO OTHERS THE RECIPT'S ORGANIZATION, EXCEPT OUTSTDE IN CONNECTIONWITH MODULES East Marion, NY 11939 THE SALE AND USE OF THE RESPECTIVE TESLA EQUIPMENT, WITHOUT THE WRITTEN IMfRiER PAGE NAME: SHEET: REV: DATE: PERMISSION OF TESLA INC. 5166727625 ESS LOCATION DETAIL 5 11/4/2025 �� � x Label Location: Label Location: x , a � 1 € E� j iak (BLC) r �°� )I `}` (MSP) ) Per Code: r �_ � xxw ° ; Per Code: r ' �t 408.4 =�,�,� ���d������� � �����`� "��� 705.12.6.3 ` Label Location: (BLC} Per Code: x f: Label Location: 220 fi (MSP) Per Code: IN 705.12.B.2.3.c P ° y "'""°�' { � Label Location: (MSP) .'.''�.4 1" Per Code: r � 11w o v312.8.A.3' . , ,.43 a�pF( ,{ C ; e�u ... £� � r !- *SCa h x w w r a z Label Location: Label Location: (MSP) (MSP) Per Code: N l Per Code: f � _ 706.7.D(Label to be marked in field per code) fie. a 705.12.B.3 Label Location: (MSP) Per Code: 706.7.E Label Location: � �'kP'xg. y 3•� •` °" -' � ��� (MSP) Per Code. � t � 1 Label Location: � - (MSP) Per Code: 706.7.E r Label Location: x (MSP) Per Code: 706.7.E * (AC):AC Disconnect (BLC): Backup Load Center (MSP): Main Service Panel NEC 2017 - Default Label Set 00 "Powerwall 3 Powerwall S Technical Specifications System Technical Model Number 1707000-xx-y _.....__..,.._..w...:. -.-.»- _. .,..._T_. ...�.._....__._._._. _.. Specifications Nominal Grid Voltage(Input&Output) 120/240 VAC Powerwall 3 is a fully integrated solar and battery system,designed to accelerate the transition to sustainable energy. Grid Type_ Split phase Frequency..._�.__._..,�....._...__._„y......,._...,.....,.,.:_.....,._.....,.._.�.�.._,._.._._...,,......�_.�_.,.....,..,•-_....,_....._,__,....w..,,.......rvw.,_.,_._w_.,_,�_..:.__.w�._.._.w_.__.,.....,_..-._... . Customers can receive whole home backup,cost savings,and energy independence by producing and consuming their 60 Hz own energy while participating in grid services,once installed,customers can manage their system using the Testa App to Nominal Battery Energy 13.5 kWh AC customize system behavior to meet their energy goals. __.,._„•_-...._.,_. _.. __..-�__......_.._. . .._.__.,�_.._.,-_....._...____,.____...,�__ ._........,_ Nominal Output Power(AC) 5.8 kW 7.6 kW 10 kW 11.5 kW Powerwall 3 achieves this by supporting up to 20 kW DC of solar and providing up to'11.5 kW AC of continuous power per Maximum Apparent Power 5,800 VA 7,600 VA 10,000 VA 11,500 VA unit, It has the ability to start heavy loads rated up to 185 LRA, meaning a single unit can support the power needs of most Maximum Continuous Current 24 A 31.7 A 41.7 A 48 A homes. Powerwall 3 Expansions make it easier and more affordable to scale up custoiYiers'systems to meet their current or feature needs.Powerwall 3 is designed for fast and efficient installations, modular system expansion,and simple connection to Overcurrent Protection Device �_._...30 A M W ey.__ _40„A..._.....„ _6�nA ^. � 6�A.._._..�__.....,...._., .,....._.�,...�M......evi _.._..-_T any electrical service. Configurable Maximum Continuous Discharge 15.4 kW 3 Power Off-Grid(PV Only,-20°C to 25°C) Maximum Continuous Charge Current/Power Y20.8 A AC/5 kW (Powerwall 3 only) Maximum Continuous Charge Current/Power 33.3 A AC/8 kW (Powerwall 3 with up to(3)Expansion units) Output Power Factor Rating w 0-1(Grid Code configurable)T _ Maximum Output Fault Current(1 s) 160 A y•� �^~��~� _�-��"._- . -, ._. g Maximum Short-Circuit Current Rating 10 kA 9 „x Load Start Capability 185 LRA s Solar to Battery to Home/Grid Efficiency 89%1' cr. J Solar to Home/Grid Efficiency 97.5%5 Power Scalability Up to 4 Powerwall 3 units supported Energy Scalability Up to 3 Expansion units(for-a maximum total of 7 units) .�...... . y Supported Islanding Devices Gateway 3,Backup Switch,Backup Gateway 2 Connectivity Wi-Fi(2.4 and 5 GHz) Ethernet Cellular(LTE/4G ) Y Hardware Interface Dry contact relay,Rapid Shutdown(RSD)certified switch fw � and 2-pin connector,RS 485 for meters d. \ rz ,,, t. , ,� .� �, �s� �, ' AC Metering Revenue Grade(+/ 0 5% ANSI C12 20) Protections Integrated arc fault circuit interrupter(AFCI),Isolation Monitor Interrupter(IMI),PV Rapid Shutdown(RSD)using Testa Mid-Circuit Interrupters _u..� Customer Interface Testa Mobile App II Warranty 10 years 'Values provided for 25°C(770F),at beginning of life.3.3 kW charge/discharge power. zSee Powerwall 3 Installation Manual for fuse requirements if using fuse for overcurrent protection. 31f enabling the 15.4 kW off-grid maximum continuous discharge power,Powerwall 3 must be installed with an 80 A breaker and appropriately sized conductors. " 'Typical solar shifting use case. STested using CEC weighted efficiency methodology. 'The customer is expected to provide internet connectivity for Powerwall 3;cellular should not be used as the primary mode of connectivity.Cellular connectivity subject to network operator service coverage and signal strength. i 2024 2024 PG4Voiw,)H 3 i;ata.,,heat • Powerwall 3 Technical Specifications Powerwall 3 `technical Specifications Solar Technical Maximum Solar STC Input 20 kW Mechanical Dimensions 1105 x 609 x 193 mm(43.5 x 24 x 7.6 in) _._ .._......_. _,.__. ....__..� ..w_.,,.M .._,M.,W. .,,_..._.,... �..._.._.,_�_..._,_ ._.w......_._,_......M_,.,_. _..._ -,....,. Specifications Withstand Voltage 600 V DC Specifications Total Weight of Installed Unit 132 kg(291.2lb) PV DC Input Voltage Range 60 550 V DC Weight of Powerwall 3 124 kg(272.5 lb) PV DC MPPT Voltage Range 60—480 V DC Weight of Glass Front Cover 6.5 kg(14.5 IN MPPTs 6 Weight of Wall Bracket 1.9 kg(4.2 lb) Maximum Current per MPPT(1 ) 13 A7 Mounting Options Floor or wall mount Maximum Short Circuit Current per MPPT(1_) 15 A7 aThese dimensions include the glass front cover being installed on Powerwall 3. Where the DC input current exceeds the MPPT rating,a jumper can be used to combine two MPPTs into a single input to intake _ DC current up to 26 A IMP/30 A Isr. 77 � a EnvironmentalOperating Temperature _ _ _ _-20°C to 50°C(-4°F to 122°F)8 Specifications Operating Humidity(RH) m - M,. ^ - Up to 100%,condensing Storage Temperature -20°C to 300C(-4°F to 861F),up to 95%RH,non- condensing,State of Energy(SOE):25%initial 1105 r_.._....._M.w..._..,. _._.,. _w._.. __._. v..__... Maximum Elevation 3000 m(9843 ft) Environment Indoor and outdoor rated Enclosure Rating NEMA 3R Ingress Rating IP67(Battery&Power Electronics) IP55(Wiring Compartment) Pollution Rating PD3 Operating Noise @ 1 rn <50 db(A)typical 609 mm 193.'1 <62 db(A)maximum min I _ .-..._. 8 Performance may be de-rated at operating temperatures above 40°C(104°F). Compliance Certifications UL 1741,UL 9540,UL 9540A,UL 3741,UL 1741 PCS, Information UL 1741 SA,UL 1741 SB,UL 1973,UL 1699B,UL 1998, GSA C22.2 No.0.8,CSA C22.2 No.107.1,CSA C22.2 No. 330,CSA 22.3 No.9,IEEE 1547,IEEE 1547A,IEEE 1547.1, CA Rule No.21 Grid Connection United States and Canada Emissions FCC Part 15 Class B,ICES 003 Environmental RoHS Directive 2011/65/EU Seismic AC156,IEEE 693-2005(high) Fire Testing Meets the unit level performance criteria of UL 9540A 2024 Powor%will 3 Datashee3t 2024 Flowerwail 3 D'c'z.she at Powerwall 3 Expansion Technical Specifications Powerwall 3 Example System Configurations Battery Technical Model Number 1807000-xx y Powerwall 3 with Gateway 3..,.......>,..._......,. .................._.....�,..._._.___»._....._ _..,._...__....,..._...,.__...„.__...�.._......_........._..<.. _...,-.... ...........,......».._.._.r,,......_......,,..,.,.,,_ »... IOpfrona! p V13.5I I � eClfiCatians 'nelRant e...w��eYgy kWh Whole Home Backup Volta .�..-............._.._,. ,,..._., .,.�u,._....,...._ I �� 1 g g 52 92 V DC" I �L= I "Powerwall 3 Expansion units are connected in parallel and are not field serviceable. i -Solar -I 9 Operating Temperature -20°C to 50°C(-4°F to 122°F)t2 Meter Environmental _.....-_._, �...__._�,._.....__... ......_._.___.___ ..._�.._ .w_..._._.,_w_..,....___ _..__,._.....__r.._..__._.__ ,_.._ -.._._. .._..,.._...__._.....__...__. ._._. 4) Specifications Operating Humidity(RH) Up to 100%,condensing Grid Meter socket panel Gateway 3 Load center Storage Temperature -20 C to 30 C(-4 F to 867),up to 95/o RH,non- condensing State of Energy(SOE) 25%initial Maximum Elevation 3000 m(9843 ft) = Environment Indoor and outdoor rated Backup loads Powerwall 3 Enclosure Rating NEMA 3R Ingress Rating IP67 Pollution Rating PD3 Powerwall 3 with Backup Switch ..-------- __, ....._.._.__ , ._ _ .._.__.._...__... ...__.�.a 72 Performance may be de-rated at operating temperatures above 40°C(104°n. _ (Optional- Whole Home Backup I 1 Compliance Certifications UL 1973,UL 9540 Backup Switch Information I —solar Meter Grid Meter socket panel Load center I Mechanical Dimensions 1105 x 609 x 168 mm(43.5x24x6.6in)13 Specifications ......_..w_._,__.�...._�..�,,.,..�.....__.__.,.._,..._.,..........._...._...._.»....._.._.. Total Weight of Wall- Mounted Expansion Unit p Powerwall kg(261.2 lb) Backu loads Poerwall 3 qtj Weight of Expansion Unit 110 kg(242.5 lb) Weight of Glass Front 6.5 kg(14.5 lb) ~ Cover ..—� -,._ .. _ _"---,.._r.,_.-.—,l-.. Powerwall 3 with Backup Gateway 2 (Optional— —1 Weight of Wall Bracket 1.9 kg(4.2 lb) 1105 _..._ .,._...__.......__,._.,_ __._ ,._._ ....._.._,,..._._......_._.... _......._ ._._ ___ Partial Home Backup I I Weight of Expansion 0.7 kg(1.5 lb) Accessories l Mounting Options Floor or wall mount Utility Meter w._,.,...._...._.......__....._,_.w.._.,.�.,.._._...H_......,",,...._........�,...,....___-�_.,_......_.._...�.,._.._._._, I -Solar _I Stacking Capability Up to(3)Expansion units Main .(.,,Floor Moun.t_O,n,ly) behind a Powerwall 3 Breaker Compatibility with Only compatible with v Other Systems Powerwall 3 Connection to Powerwall 3 Expansion Grid Meter load center Backup Gateway 2 Load center Powerwall dimensions include nhe harness14 I I installed a Powerwall 3 Expansion.the lfront 609 mm 168 13glass front cover being mtn The Powerwall 3 Expansion harness is a listed component of the UL 9540 certification. Non-essential loads Backup loads Powerwall 3 2024 C. hsek t(rvc�,t+rdcai"� :!Ra 2024 i o"uonvrl�i • Powerwall 3 Example System Configurations Powerwall 3 with Gateway 3 (1)Powerwall 3 with(3)Expansion Units Solar Meter 1 Grid Meter socket panel Gateway 3 Load center nI Backup loads Powerwall 37 POW,:M,wail 3 Expar,�Jcn P ow P.ow a I S Powt-'r%vaif 3 Expa-lMo'n, -�Pans4on Powerwall 3 with Backup Switch (4)Powerwall 3 Units with(3)Expansion Units(Maximum System Size) FTI L LJ LLJ II/E I= Backup Switch Solar Solar Solar Solar Grid Meter socket panel Load center ter Generation panel -r--W-j Backup loads Powerwali 3 Powerwall 3 Powerwall 3 Powerwall 3 ",Lpal rl h'KPzvIMorI 2024 P Dwv,.-Aa'l 3 2024 Powewafl 3 s Gateway 3 Tesla Gateway 3 controls connection to the grid in a Powerwall system,automatically detecting outages and providing seamless transition to backup power.It provides energy monitoring that:is used by Powerwall for solar self-consumption, time-based control.and backup operation. Performance Model Number 1841000-01-y AC Meter Revenue accurate(+/-0.5%) Specifications Nominal Grid Voltage 120/240 V AC Communication CAN Grid Configuration Split phase User Interface Tesla App Grid Frequency 60 Hz Backup Transition Automatic disconnect for seamless backup Continuous Current 200 A Rating Overcurrent 100-200 A Protection Device Service entrance rated Maximum Supply_„_ 22 kA with Square D or Eaton CSR, BWH,or BW, or Short Circuit Current Eaton main breaker Square e D QOM breakers 25 kA with Eaton main _. _.__ breakers breaker' w......_. breaker' Internal Panelboard 200 A IEC Protective Class Class I µ 8-space/16 circuit breakers _ --.._._... _._.. _.._ m .. ..___.__._...-..__., ._. ..__,_-. az Eaton BR,Siemens QP,or Overvoltage Category Category IV Square D HOM breakers 'Only Eaton CSR or BWH main breakers are 25 kA rated rated to 10-125A Warranty 10 years Environmental Operating Temperature -20°C to 50°C(-4°F to 122°F) Specifications Operating Humidity(RH) Up to 100%,condensing Maximum Elevation 3000 m(9843 ft)..-�_.---.._..__._..,_,.___..._.___._..._..-._._.._.___._... Environment.._...____..-.-._...._....___._._..._.._..�-,.____..__._.M_.,._...�,._._..._._.__�.__..�.�._.,._.,._._�...___......._..,...._.,..-______.,.___._._,_.�.__._.__.._..__, Indoor and outdoor rated Enclosure Type NEMA 3R Compliance Certifications UL 67, UL 869A,UL 916, UL 1741 PCs, Information _ .. CSA 22.2107.1,CSA 22.2 29 Emmissions..._-__,..,_.....-..._.._......,_u..____.______....._.._.........._...._.-_.FCC Part 15,ICESV003....._.._,-.,____..,____._..,..,._...._...............�.._. Mechanical Dimensions 660 x 411 x 149 mm Specifications _ (26 x 16 x 6 in) Weighty 16.4 kg (36 1b).A. ._N. Mounting options Wall mount" 660 mm 411 mm �mm Gatcway 3 Datasheet 2023