HomeMy WebLinkAbout52373-Z *Of Solo T Town of Southold
* P.O. Box 1179
oAll 53095 Main Rd
Southold, New York 11971
CERTIFICATE OF OCCUPANCY
No: 46720 Date: 12/09/2025
THIS CERTIFIES that the building SOLAR PANEL
Location of Property: 7015 Bridge Ln Cutchogue, NY 11935
Sec/Block/Lot: 84.4-6.6
Conforms substantially to the Application for Building Permit heretofore,filed in this office dated: 09/10/2025
Pursuant to which Building Permit No. 52373 and dated: 10/20/2025
Was issued, and conforms to all of the requirements of the applicable provisions of the law.
The occupancy for which this certificate is issued is:
Roof-mounted solar panels to an existing single-family dwelling as applied for.
The certificate is issued to: David Comando , Debra Ginty-Comando
Of the aforesaid building.
SUFFOLK COUNTY DEPARTMENT OF HEALTH APPROVAL:
ELECTRICAL CERTIFICATE: 114263 11/13/2025
PLUMBERS CERTIFICATION:
LhoOed Signatur
�otof Sao ryo`o TOWN OF SOUTHOLD
BUILDING DEPARTMENT
• SOUTHOLD, NY
BUILDING PERMIT
(THIS PERMIT MUST BE KEPT ON THE PREMISES
WITH ONE SET OF APPROVED PLANS AND SPECIFICATIONS
UNTIL FULL COMPLETION OF THE WORK AUTHORIZED)
Permit#: 52373 Date: 10/20/2025
Permission is hereby granted to:
David Comando
7015 Bridge Ln
Cutchogue, NY 11935
To:
install roof-mounted solar panels to an existing single-family dwelling as applied for.
Premises Located at:
7015 Bridge Ln, Cutchogue, NY 11935
SCTIVI#84.4-6.6
Pursuant to application dated 09/10/2025 and approved by the Building Inspector.
To expire on 10/20/2027.
Contractors:
Required Inspections:
Fees:
SOLAR PANELS $100.00
CO-RESIDENTIAL $100.00
Total $200.00
J
------ --- ---
---------------
Building Inspector
NASSAtU ELECTRICAL
SUFFOLK INSPFCT0RS
159 Route 25A, Building 1 Suite B
Miller Place,NY 11764
Telephone:631 495 8136 - Fax:631 509 4538 • E-Mail:Requests@SuffolkBEI.com
CERTIFICATE OF ELECTRICAL COMPLIANCE
Applicant: Harvest Power LLC Certificate No.: 114263 I
Rough In Inspection Date: Final Inspection Date: Nov 13,2025
Application No.: Building Permit No.: 52373
County Tax Map No.: 084.00 01.00 006.006 ff, i
This Certificate of Electrical Compliance is limited to the inspection and compliance of eleclrjcal equipment and/or work described
below,installed on behalf of the applicant named above,located at the premise of and ngt,a er the final insp ctionn to abbvej
Owner: David Comando .3
Site Location: 7015 Bridge Lane,Cutchogue,NY 11935 , ' trrier s
a7 gFt l%t; U�
Owner's Address(if different): A =a
®Residential O Indoor ❑Basement ❑Service ❑Shed
❑Commercial 0 Outdoor ❑First Floor ❑Pool ❑Hottub
❑New ❑Renovation ❑Second Floor ❑Attic ❑Garage
❑Addition ❑Survey ®.PV Solar ❑Generator ❑Conversion
❑Signs ❑Battery Storage Safety Inspection Other:
INVENTORY
Single Phase Heat Duplex Recpt Ceiling Fixture Dual Func Breaker
Three Phase Hot Water GFCI Recpt Wall Fixture Smoke
Main Panel AC Cond Single Recpt Recessed Fixture CO Detect
Sub Panel AC Blower Range Recpt LED Lighting Smoke CO Combo
Transformer Appliance Ckt Dryer Recpt Emergency Time Clock
Disconnect 1� Switches Twist Lock Exit Fixtures Pumps
GFCI Breaker Heat Pump Electric Heat Pool Luminaire Exhaust Fan
Other Equipment:System Size:9.1 kW Qty:20 Desc:Canadian Solar CS6.1-54TM455H Qty:20 Desc:Enphase IQ7HS-66-M-US
The electrical work and/or equipment described above were inspected and was found to be in compliance with local,
state and national electrical code requirements and this office.
Applicant: Harvest Power LLC License No.: ME-68518
Date Printed: Nov 13,2025
Inspected By:Joe Coppola"
Signature: Y
OF SOUTyO�
# TOWN OF SOUTHOLD BUILDING DEPT.
cou�+� 631-765-1802
INSPECTION
[ ] FOUNDATION 1ST/ REBAR [ ] ROUGH PLBG.
[ ] FOUNDATION 2ND [ ] INSULATION/CAULKING
[ ] FRAMING/STRAPPING- [ gFINAL �
[ ] FIREPLACE & CHIMNEY [ ] FIRE SAFETY INSPECTION
[ . ] FIRE RESISTANT CONSTRUCTION [ ] FIRE RESISTANT PENETRATION
[ ] ELECTRICAL-(ROUGH). [ ] ELECTRICAL (FINAL)
[ ] CODE VIOLATION [ - ] PRE C/O [ ] RENTAL
REMARKS: o
DATE- INSPECTOR
Graham Associates 256 Orinco Dr, Brightwaters, NY 11718
Building Consultants & Expeditors (631) 665-9619 Fax (631) 969-0115
November 17, 2025
Town of Southold Building Department
Post Installation Certification
Comando Residence — 7015 Bridge Lane, Cutchogue, New York 11935
Permit # 52373
Installation Date: 11/3/2025
Inspection Date: 11/7/2025
To Whom It May Concern,
The roof mounted photovoltaic system at the above referenced residence has
been installed properly in accordance with the approved plans and is
certified by Michael K. Dunn, RA, to be in compliance with the minimum
requirements of the 2020 New York State Residential Building Code; Town
Local Code, Long Island Unified Solar Permit Initiative, (LIUSPI); and
2020 National Electric Code NFPA 70/2020 National Electric Code
including ASCE7-16.
If you have any further questions, do not hesitate to call.
('\S- eREDgR
1 EL A-o '�i�,
y029BAl ��-
OF NEW-�O
Michae unn, RA
FIELD INSPECTION REPORT I DATE COMMENTS
Q .d
FOUNDATION (1ST) -- w
--------------------------------------
FOUNDATION (2ND) --- ��
ROUGH FRAMING& —
PLUMBING
(O
INSULATION PER N.Y.
STATE ENERGY CODE
FINAL
ADDITIONAL COMMENTS
�`��-�- 5 1615 G 1� � �-• - � z
�m
X
N o
---- J z
— — x
- d
ro
1 Y
,o+aAt' f0tt�o� TOWN OF SOUTHOLD-BUILDING DEPARTMENT
Town Hall Annex 54375 Main Road P. O. Box 1179 Southold,NY 11971-0959
Telephone (631) 765-1802 Fax(631) 765-9502 https://wwwsoutholdtownny:gov
Date Received
APPLICATION FOR BUILDING PERMIT
For Office Use Only
SEP � � 2025
PERMIT NO. Building Inspector:
Applications and forms must be filled out in their entirety.Incomplete _S J,T
rv;efi<<, •
applications will not be accepted. Where the Applicant is not the owner,an
Owner's Authorization form(Page 2)shall be completed.
Date: 2g ?•Jr
OWNER(S)OF PROPERTY:
Name:.Comando, David SCTM#1000- L� .�V I �0 "OZ.00
C�
Project Address: -70 15 �C � C J,�Woe-, ky 11 9 3S Wl
Phone#: 691) 7LI I- rj_I/-I Email: 8.CLV . ain af40 @ JC(na.`( Co A-)
Mailing Address:
CONTACT PERSON:
Name: GhC�.el -
MailingAddress: 2941 Sunrise Hwy, Islip Terrace, NY 11752
Phone#: (631) 647-3402 Email: hppermitting@harvestpower..net
DESIGN PROFESSIONAL INFORMATION:
Name: Michael Dunn, R.A.
Mailing Address: 256 Orinoco Dr, Brihtwaters, NY 11718
Phone#: (631) 665-9619 Email: Glenn@grahamassociates .com
CONTRACTOR INFORMATION:
Name: Harvest Power LLC
Mailing Address: 2941 Sunrise Hwy, Islip Terrace, NY 11752
Phone#: (631) 647-3402 Email: hppermitting@harvestpower.net
DESCRIPTION OF PROPOSED CONSTRUCTION
El New Structure Addition❑✓ Alteration ❑Repair ❑Demolition Estimated Cost of Project:
❑other y-r_ $ 531 100
Will the lot be re-graded? ❑Yes ®No Will excess fill be removed from premises? ❑Yes ONO
1
PROPERTY INFORMATION
Existing use of property: Residence Intended use of property. (no change)
Zone or use district in which premises is situated: Are there any covenants and restrictions with respect to
this property? ❑Yes ®No IF YES, PROVIDE A COPY.
Check Box After Reading: The owner/contractor/design professional Is responsible for all drainage and storm water issues as provided by'
Chapter 236 of the Town Code. APPLICATION IS HEREBY MADE to the Building Department for the issuance of a Building Permit pursuant to the Building Zone
Ordinance of the Town of Southold,Suffolk,County,New York and other applicable Laws,Ordinances or Regulations,for the construction of buildings,
additions,alterations or for removal or demolition as herein described.The applicant agrees to comply with all applicable laws,ordinances,building code,
housing,code and regulations and to admit authorized inspectors on premises and in building(s)for necessary inspections.False statements made herein are
punishable as a Class A misdemeanor pursuant to Section 210.45 of-the New York State Penal Law,
Application Submitted By( t name): ❑✓ Authorized Agent ❑Owner
Signature of Applicant: Date: �'L`t
STATE OF NEW YORK)
C SS:
COUNTY OF 51,XXO bl.
AtCh ae,I CA( being duly sworn,deposes and says that(s)he is the applicant
(Name of individual signing contract)above named,
(S)he is the AG !?n
(Contractor,Agent, Corporate Officer,etc.)
of said owner or owners, and is duly authorized to perform or have performed the said work and to make and file this
application;that all statements contained in this application are true to the best of his/her knowledge and belief; and
that the work will be performed in the manner set forth in the application file therewith.
Sworn before me this
olay of 66157— ,20
NMaWfiIBIDbtic,State of New York "
No.01MA492SO56
Qualified in Suffolk Cow
Term expires �
PROPERTY OWNER AUTHORIZATION
�(1NFie�he apphcan"�"�'is not t ie owne ,
I, Dwia Co P-m A residing at 701S line CUTChojvt
J 2 I
7 c�S do hereby authorize Kiaag( C41 '16 ,c- to apply on
my behalf to the Town of Southold Building Department for approval as described herein.
w Date
Conn
0 �U 1� a In A�
Print Owner's Name
2
I
Building Deparment Application
AUTHORIZATION
(Where the Applicant is not the Owner)
i
CLy{L Co fv\CAdo residing-at: 701 S �C t LOLn( ,
(Print property owner's name) (Mailing Address).
CV hOQ VC, y , ,q35 do hereby authorize M j G h&e 1
—�— (Agent)
Harvest: Power LLC to apply on my behalf to the
Southold Building Department.
(Owner's Signatur (Date)
(Print Owner's:Name)
1 C
CONSENT TO INSPECTION
r
U �jMC��► (� ,the undersigned, do(es)hereby state:
Owner(s)Name(s)
That the undersigned(is (are)the owner(s)of the premises in the Town of
Southold, located at 01 ; anc C l S ,
which is shown and designated on the uffo k County Tax ap as District 1000,
Section N ��Block,0l .00 , Lot �.b0 6
That the undersigned(has)(have)filed, or cause to be filed,an application in the
s Southold Town Building In ctor's Office for the following: �0IC- r—
�n� ua.t,or, of a s e 1 kw ar PV Sjmk-m w ZO
S 6. 1 -S -rM -g5SIA 200,F (h60A*-,a ?,-0j(E
That the undersigned do(es)hereby give consent to the Building Inspectors of the
Town of Southold to enter upon the above described property, including any and all
buildings located thereon,to conduct such inspections as they may deem necessary with
respect to the aforesaid application, including inspections to determine that said premises
comply with all of the laws,ordinances,rules and regulations of the Town of Southold.
The undersigned, in consenting to such inspections;do(es)so with the knowledge
and understanding that any information obtained in the conduct of such inspections may
be used in subsequent prosecutions for violations of the laws, ordinances, rules or
regulations of the Town of Southold.
I
Dated: -G
(Print Name)
(Signature)
(Print Name)
HF ,
L
HARVESTPOVJ'2a�
Harvest Power LLC i 2941 Sunrise Highway,Islip Terrace,NY 11752 1 631-647-3402 harvestpower.net
November 25, 2025
Solar Permit Closeout
- Please see Electrical Certificate and Post Install Letter
Town of Southold
r,
Permit# 52373
rA DEC - 1 2025
Customer information:
David Comando
7015 Bridge Lane
Cutchogue, NY 11935
Kind Regards,
Michael Calise
Permit Expeditor
(631) 647-3402
Mcalise@harvestpower.net
Graham Consulting Corp. 256 Orinoco Drive,Suite A Brightwaters,NY 11718
Planning&Design (631)665-9619
September 5, 2025
Town of Southold
Building Department
54375 Rt. 25
Southold, NY 11971
Re: David Comando Residence
7015 Bridge Lane
Cutchogue, NY
Proposed 9.10 kWDC, 7.68 kWAC KW PV System
To Whom It May Concern,
Please be advised that I have analyzed the existing roof structure at the
above-mentioned premises and have determined that it is adequate to
support the additional load of the solar panels and a 140 mph wind load and
20 psf snow load without overstress, in accordance with the following:
The 2020 New York State Uniform Fire Prevention and Residential Building
Code; Town of Southold Local Code, Long Island Unified Solar Permit
Initiative, (LIUSPI); and 2020 National Electric Code NFPA 70/2020
National Electric Code including ASCE7-16
If you have any further questions, do not hesitate to call.
tsTEREpq
\ 2KQ�_ 0$
O
� G �
C z
��A
\'C O `'`J817
RA
PHOTOVOLTAIC ROOF MOUNT SYSTEM
20 MODULES-ROOF MOUNTED - 9. 10 kWDC, 7.68 kWAC
HARVEST
7015 BRIDGE LN , CUTCHOGUE, NY 11935, USA ELECTRICAL HARVEST POWER LLC
- -- --_ -- 941 SUNRISE HIGHWAY ISLIP
SYSTEM SUMMARY: APP O ED AS NOTED SHEET INDEX INSPECTION ED TERRACE, 11752
GOVERNING C_O_DES. TEL:(801)989-3585
(N)20-CANADIAN SOLAR CS6.1-54TM-455H (455W) MODULES 2017 NATIONAL ELECTRICAL CODE PV-0 COVER SHEET N1>;EC bsite:www.harvest owernet
(N)20-ENPHASE IQ7HS-66-M-US MICRO-INVERTERS DA B.p# �� 20 NEW YORK STATE UNIFORM CODE PV-1 SITE PLAN WITH ROOF PLAN R G
(N)JUNCTION BOX PV-1.1 ENLARGED VIEW P OUNN
(E) 150A MAIN SERVICE PANEL WITH (E) 150A MAIN BREAKER FEE;j,z&_By.
2020 NEW YORK STATE RESIDENTIAL CODE PV-2 ATTACHMENT DETAILS �J
(N)60A FUSED AC DISCONNECT NOTIFY BUILDING DEPARTMENTAT PV-3 THREE LINE DIAGRAM W Q O
(N) ENPHASE IQ COMBINER BOX
COMPLY WITH ALL CODES OFPV-4 PLACARDS&WARNING LAB _ }
631-765-1802 8AM TO4PM FOR THE NEW YORK STATE &TOWN ODE�'S5 ADDITIONAL NOTES
FOLLOWING INSPECTIONS: AS REQUIRED AND CON IONSUP-9 SPEC SHEETS
1. FOUNDATION-TWO REQUIRED
DESIGN CRITERIA: FOR POURED CONCRETE S'nOLDT ZBA ,P
ROOF TYPE: -ASPHALT SHINGLE 2. ROUGH-FRAMING&PLUMBING _ ' ST VERSION
;:y
NUMBER OF LAYERS: - 1 3, INSULATION SOUTHO OWN PLANNING BOARD + ` �Y DESCRIPTION DATE REV.
ROOF CONDITION: O.K 4. FINAL-CONSTRUCTION MUST OLDTOWNTRUSTEES ' IS UN�.A FUL BLDG.PERMIT 09iO3/2025 0
ROOF FRAME:-2"X10" RAFTERS @16" O.C.
STORY:-TWO STORY BE COMPLETE FOR C.O. S,DEC
SNOW LOAD : -25 PSF ALL CONSTRUCTION SHALL MEET THE 1UTH00HPC WITHOUT CERTIFICATE
WIND SPEED :- 130 MPH REQUIREMENTS OF THE CODES OF NEW SCHO OF OCCUPANCY
WIND EXPOSURE:-C YORK STATE. NOT RESPONSIBLE FOR
DESIGN OR CONSTRUCTON ERRORS
GENERAL NOTES:
1. INSTALLATION IN ACCORDANCE WITH MANUFACTURER �So
RECOMMENDATIONS. PRO IC('`T SITE
2. ENGINEER TO INSPECT PROJECT AFTER INSTALLATION ARRAY LOCATION f �JEC S C
AND CERTIFY COMPLIANCE. �Ulas1i11tn�S Irlll
3. PROJECT TO BE INSTALLED WITH CODE COMPLIANT '
RACKING INSTRUCTIONS FOR UNI-RAC SOLAR MOUNT PROJECT NAME
SYSTEM. - + �Ga(, W
4. FOLLOW BALLASTING SCHEDULE ON ROOF PLAN.
5. HARVEST POWER, LLC., THE SOLAR INSTALLATION z <
CONTRACTOR, COMPLIES WITH ALL LICENSING&ALL W (.0O Q
RELATED REQUIREMENTS OF THE GOVERNING Peconic t 0 0
MUNICIPALITIES AND THE LOCAL ELECTRIC UTILITY U) - LO C:)AHJ'S. �� I W _j � O Q
6. THIS PROJECT WILL COMPLY WITH THE CURRENT NEC W p a-
REQUIREMENTS INCLUDING ARTICLE 690 SOLAR
PHOTOVOLTAIC PV SYSTEMS. , 0 0 } p I �
7. THE ROOF WILL HAVE NO MORE THAN A SINGLE LAYER 7015 Bridge Ln, C) 0 Z S O
OF ROOF COVERING IN ADDITION TO THE SOLAR m LL op ~
EQUIPMENT. Cutchogue, NY Q ::) o z
8. INSTALLATION WILL BE FLUSH-MOUNTED, PARALLEL 935, United States 25 O C)
0 00 0 0
TO AND NO MORE THAN 6.5"ABOVE ROOF U _
9. MAINTAIN A MINIMUM OF 18"CLEARANCE AT RIDGE
AND AT ONE GABLE EAVE. {� i r ds 0 C)fa z
" " . 4. it
10. THIS DESIGN COMPLIES WITH 130 MPH WIND j _Q
REQUIREMENTS OF THE RESIDENTIAL CODE OF N.Y.S i GityMD Cutchogue Q C) Q
top
AND ASCE 7-16. �. a PUrgent Care-Lon 0
11. WHEREVER THE ROOF PLAN DOES NOT COMPLY WITH �•! g...
ACCESS AND VENTILATION REQUIREMENTS OF THE • l �� SHEET NAME
UNIFORM CODE, HARVEST POWER PROPOSES THAT +.
COVER SHEET
ALTERNATIVE VENTILATION METHODS WILL BE '!' NA:
EMPLOYED. REVIEW AND APPROVAL SHALL BE AT THE 1
DISCRETION OF THE MUNICIPALITY IN WHICH THIS 4 . Wickham's Fruit Farm SHEET SIZE
DOCUMENT HAS BEEN FILED. ANSI B
12. THE DESIGN PLANS COMPLY WITH THE 2020 NEW
YORK STATE UNIFORM FIRE PREVENTION AND 11" X 17"
RESIDENTIAL BUILDING CODE. 1 AERIAL PHOTO 2 VICINITY MAP
SHEET NUMBER
PV-0 SCALE: NTS PV-0 SCALE: NTS PV_O
MODULE TYPE, DIMENSIONS & WEIGHT ROOF ACCESS AREA:
- — SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND
NUMBER OF MODULES =20 MODULES OVER OPENINGS SUCH AS WINDOWS OR DOORS,AND LOCATED AT STRONG POINTS OF
MODULE TYPE =CANADIAN SOLAR CS6.1-54TM-455H (455W) MODULES BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS POINT DOES NOT
MODULE WEIGHT=50.7 LBS/23.0 KG. CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS,WIRES OR SIGNS.
MODULE DIMENSIONS= 70.9"X 44.6"=21.96 SF
UNIT WEIGHT OF ARRAY=2.31 PSF
HARVEST
HARVEST POWER LLC
2941 SUNRISE HIGHWAY ISLIP
TERRACE,NY 11752
\/O ite( 989-3585
�GoTECsit� N e:wwww.h t owernet arves
UNJf
SEE ENLARGED - C ��u O 700 V � a'-
VIEW ON PV-1.1 ,' ��J� `��� 28, v
/ 4�;�
p
\ /QOp TAl VERSION
DESCRIPTION DATE REV.
BLDG.PERMIT 09/03/2025 0
YJ '
JI
If
• •. / Q�
(E) FENCE
C v \ ' PROJECT NAME
vJJ 1 �`J \ / /
,�'_ 1(i�� v v�/ W
(E) DETACHED �,��� '� U
Z a CD STRUCTURE J l� �� /If Lu
CD
J °' oo Q
Grprol
O } o O
�;� Z o LL
.::. Z 0� LLi � � O
l / l
C u OO J Z
O o 0 0 0
p�RTy � =
p a-
( ' - (E)TREE (TYP.) QQ U Q
SHEET NAME
28 SITE PLAN WITH
ROOF PLAN
♦ SHEET SIZE
ANSI B
11" X 17"
SITE PLAN WITH ROOF PLAN SHEET NUMBER
SCALE: 1/32"= 1'-0" PV-1
MO.DULE,TYPE_, DIMENSIONS & WEIGHT ROOF ACCESS AREA:
NUMBER OF MODULES =20 MODULES SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND
=50.7 LBS/23.0 KG.
OVER OPENINGS SUCH AS WINDOWS OR DOORS,AND LOCATED AT STRONG POINTS OF
MODULE WEIGHT= 0.7
MODULE TYPE= AN SOLAR CS6.1-54TM-455H (455W) MODULES /' `���� BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS POINT DOES NOT
MODULE DIMENSIONS- 70.9"X 44.6"-21.96 SF �`` CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS,WIRES OR SIGNS.
UNIT WEIGHT OF ARRAY=2.31 PSF J
HARVEST"
(E) UTILITY METER HARVEST POWER LLC
2941 SUNRISE HIGHWAY ISLIP
TERRACE,NY 11752
(E) 150A MAIN SERVICE PANEL HITEC
/ site:www.hary st3ower.net
/ �� � WITH (E) 150A MAIN BREAKER p�
<`. / (INSIDE BASEMENT) p O N N
Cy-
(N) 60A FUSED AC DISCONNECT �_ ^ O
1
i (N) ENPHASE IQ COMBINER BOX '441
(N) 1" PVC CONDUIT i O�
STAB
RUN 7/8"ABOVE ROOF i
1 VERSION
(N) JUNCTION BOX / 1 DESCRIPTION DATE REV.
/ [�
BLDG.PERMIT 09/03/2025 0
If t
If If
' G
v�Q R `SS
✓e yQ STQ PROJECT NAME
����/ ♦ �SF Ry w
U
♦ ♦ z � c° o
♦ ♦ Lu o J
CD
♦ ♦ ♦ wZMo I=-
44P ♦ Jrn o
CODE ♦ ♦ LLI r O a- O
F
ggFqss O p (D } o J cn
♦ ♦ 0 Z p � LL.
Z IY- 'T O
♦ ♦ QmLuo �
o
ROOF#1 ♦ O o U CD(20) CS6.1-54TM-455H (455W)
U � O o O
RAFTERS= 2"X10"@16" O.0
214'AZIMUTH, 33'TILT F__ Z �
(E) CHIMNEY (TYP.)
Q U Q
(20) ENPHASE IQ7HS-66-M-US - Q
MICRO-INVERTERS
SHEET NAME
ENLARGED
VIEW
SHEET SIZE
ANSI B
11" X 17"
EN LARG E D VIEW SHEET NUMBER
SCALE: 3/32"= 1'-0" PV-1 . 1
J
PV MODULES
Xl-
HARVESTPOWF-
HARVEST POWER LLC
2941 SUNRISE HIGHWAY ISLIP
TERRACE,NY 11752
- TEL:(801)989-3585
SEE ENLARGED VIEW OG }� 1` websitemww.harvestpower.net
6 GN T
UN&
(E) ASPHALT SHINGLE ROOF y
0
GENERAL NOTES: VERSION
1. RAILS TO BE INSTALLED TWO PER PANELS AS SHOW DESCRIPTION DATE REV.
2. ALL PENETRATIONS TO BE MADE@ 48" O.C. BLDG.PERMIT 09/03/2025 0
3. BOLTS TOBE INSTALLED INTO RAFTERS.
4. MINIMUM 2.5" PENETRATION INTO WOOD FOR CODE COMPLIANCE.
1
ATTACHMENT DETAIL NOTE:-
"ACTUAL ROOF CONDITIONS AND RAFTERS (OR SEAM) LOCATIONS MAY
SCALE: NTS VARY. INSTALL PER MANUFACTURER(S) INSTALLATION GUIDELINES
AND ENGINEERED SPANS FOR ATTACHMENTS."
END / MID CLAMP PV MODULES
PROJECT NAME
LL1
U
00 ccl? Z
W o
Q J
O O
U-) O =
Z COCDf-
W -J 0-) CD Q
L-FOOT LLI r o a O
OCR } o -icn
0 Qz o } LL
t (E) ASPHALT SHINGLE ROOF Z m LLI 4- J O
u2 `-) C� o H
(N) UNIRAC ROOF/ DECK MEMBRANE O O o O
SM STANDARD RAIL
> > 0- _
Q
(E) 2"X10" RAFTERS @ 16" O.0 U
2.5" MIN.
EMBEDMENT SHEET NAME
ATTACHMENT
FLASH KIT PRO FLASHING DETAILS
SHEET SIZE
BUILDING STRUCTURE ANSI B
5/16" STAINLESS STEEL LAG BOLT 11" X 17"
WITH SS EPDM BONDED WASHER,
ATTACHMENT DETAIL (ENLARGE VIEW_) - - 2-1/2" MIN. EMBEDMENT. SHEET NUMBER
SCALE: NTS PV-2
(20) CAIVADIAN SOLAR CS6.1-54TM-455H(455W) MODULES BILL OF MATERIALS
(20) ENPHASE IQ7HS-66-M-US MICRO-INVERTERS EQUIPMENT QTY DESCRIPTION
(02) BRANCHES OF 10 MODULES CONNECTED IN PARALLEL PER BRANCH SOLAR PVMODULE 20 CANADIAN SOLAR CS6.1-54TM-455H(455W)MODULES f1p
- -- - - - _ INVERTER 20 ENPHASE IQ7HS-66-M-US MICRO-INVERTERS
COMBINER BOX 1 ENPHASE IQ COMBINER BOX
JUNCTION BOX 1 600V,55A MAX,4 INPUTS,MOUNTED ON ROOF FOR WIRE&CONDUIT TRANSITION HARVESTPOWER
SYSTEM SIZE:-20 x 455W= 9.10 kWDC HARVEST POWER LLC
20 x 384VA- 7.68 kWAC AC DISCONNECT 1 AC DISCONNECT 60A FUSED,WITH 40A/2P FUSES,240V NEMA 3R, 2941 SUNRISE HIGHWAY ISLIP
TERRACE,NY 11752
PGµ Cr TERRACE,
(801)989-3585
Q 4-9 N websltemww.harvestpower.net
U h O
STAGE G
VERSION
DESCRIPTION DATE REV.
BLDG.PERMIT 09/03t2025 0
10 MICRO-INVERTERS IN BRANCH CIRCUIT#1
.
TO UTILITY GRID
L1L2N
III - I (N)ENPHASE
I I - I COMBINER BOX
ti I I ti- ` -J------------- ` -J ----- UTBI-ILITY
1 M UTILITY METER
SUPPLY SIDE TAP 1-PHASE,3-W,
10 MICRO-INVERTERS IN BRANCH CIRCUIT#2 1 120V/240V
HE I 15A
. . . (N)JUNCTION BOX (N)AC DISCONNECT 60A
FUSED,VISIBLE LOCKABLE PROJECT NAME
j LABELED,40A FUSES, w
20A 240 VAC U
1-411
Q
^, I 20A 40A FUSES 150A W O�'J---------- -----; L1 L1 0 - CD
-- j (E)150A MAIN U) O =
L1 L1 L2 L2 o SERVICE PANEL LLI Z Cr) O
W/(E)150A J O Q
(20) ENPHASE IQ7HS-66-M-US i 2 a IO N N o MAIN BREAKER LLJ � d
ENVOY
MICRO-INVERTERS i �--------- --- ------ G ------ -- ----------, o (TOP FED) 0 0 } O J Cn
LL
TERMINATOR CAP ON LAST CABLE L---- - -, -- -- r
__ N I (INSIDE Q �_ z OG G I BASEMEN }---- i i N Q Co w ob
H
CONNECTOR Q-CABLE (TYP) L______________ ___j i G] O o :D 00
(2)Q-CABLE (4)#10 AWG THWN-2 (3)#6 BLK RED THHN (2)#6 BLK RED THHN L----------- - U O �>
(1)#6 THHN STRANDED (1)#6 WHT THHN _
(1)PV 6 BARE CU GND (1)#6 THHN STRANDED GREEN GROUND IN 1"PVC (1)#6 THHN STRANDED _- 0 U * �
GREEN GROUND � Z
IN 1" PVC CONDUIT CONDUIT RUN GREEN GROUND IN 1"PVC GROUNDING � � a =
CONDUIT RUN ELECTRODE SYSTEM Q U 0- Q
0
SHEET NAME
THREE LINE DIAGRAM
SHEET SIZE
ANSI B
11" X 17"
THREE LINE DIAGRAM SHEET NUMBER
1 - -
SCALE: NTS PV-3
4'' `
AWARNING AWARNINGI
ELECTRICAL SHOCK HAZARD PHOTOVOLTAIC SYSTEM SOLAR PV SYSTEM EQUIPPED fp
COMBINER PANEL WITH RAPID SHUTDOWN
TERMINALS ON LINE AND LOAD DO NOT ADD LOADS HARVESTPOWER
SIDES MAY BE ENERGIZED IN HARVEST POWER LLC
THE OPEN POSITION LABEL LOCATION: 2941 SUNRISE HIGHWAY ISLIP
PHOTOVOLTAIC AC COMBINER(IF TERRACE,NY 11752
APPLICABLE). TEL:(801)989-3585
LABEL LOCATION: �s website:wwwhen/estpower.net
INVERTCOMBI ERSPANED((IF APPLICABLE). 3 TURN RAPID SHUTDOWN
SWITCH TO THE"OFF" SOLARELECTRIC USN
PV PANELS
POSITION TO SHUT DOWN � r
PV SYSTEM AND REDUCE 2� Y
SHOCK HAZARD IN THE v cr-
ARRAY. O
RAPID SHUTDOWN SWITCH
'FAT VERSION
• • • ' • PV SYSTEM DESCRIPTION DATE REV.
LABEL LOCATION: BLDG.PERMIT 09/03/2025 0
ON OR NO MORE THAT 1 M(3 FT)FROM THE SERVICE
LABEL LOCATION: DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
UTILITY SERVICE ENTRANCE/METER,INVERTER/DC ARE CONNECTED.
DISCONNECT IF REQUIRED BY LOCAL AHJ,OR
OTHER LOCATIONS AS REQUIRED BY LOCAL AHJ.
AWARNING
POWER SOURCE OUTPUT CONNECTION
DO NOT RELOCATE THIS
PROJECT NAME
OVERCURRENT DEVICE
W
LABEL LOCATION: U
ADJACENT TO PV BREAKER AND ESS W � O
OCPD(IF APPLICABLE). —_ -- J
BUILDING SUPPLIED BY UTILITY C) coo 0
GRID AND PHOTOVOLTAIC w Z co o Q
SYSTEM
w � � a
O
Z o J w
PHOTOVOLTAIC z m LLi �25
LABEL LOCATION:
0 0 0 0
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, LU �—
AT EACH TURN,ABOVE AND BELOW PENETRATIONS, (D
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. B Z =
m B
Q U Q Q
o (N)PV MODULES Q
r
PHOTOVOLTAIC AC DI • SHEET NAME
OPERATINGMAXIMUM AC CURRENT:
•VOLTAGE: , (E)UTILITY METER PLACARD &
„ (E)MAIN SERVICE PANEL
VAC (INSIDE BASEMENT WARNING
NOMINAL OPERATING LABELS]
LABEL LOCATION: (N)FUSED AC DISCONNECT SHEET SIZE
AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF (N)COMBINER BOX ANSI B
INTERCONNECTION. 1 1" X 1 7„
LABEL LOCATION: SHEET NUMBER
POINT OF INTERCONNECTION
(PER CODE:NEC690.56(B),NEC705.10,225.37,230.2(E)) PV-4
1. EACH MODULE TO BE GROUNDED USING THE SUPPLIED CONNECTION POINT PER
MANUFACTURER'S REQUIREMENTS. ALL SOLAR MODULES, EQUIPMENT, AND H11
METALLIC COMPONENTS ARE TO BE BONDED. IF THE EXISTING GROUNDING HARVEST
ELECTRODE SYSTEM CAN NOT BE VERIFIED OR IS ONLY METALLIC WATER PIPING, HARVEST POWER LLC
IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL 2941TERRISE,NY117YISLIP
.�`'� TERRACE,NY 11752
GROUNDING ELECTRODE. �` , �7 �1 TEL (601)989-3585
we bsite:www.ha rvestpo wer.net
2. ALL PLAQUES AND SIGNAGE REQUIRED BY THE LATEST EDITION OF NATIONAL
ELECTRICAL CODE. LABEL SHALL BE METALLIC OR PLASTIC, ENGRAVED OR r o
MACHINE PRINTED IN A CONTRASTING COLOR TO THE PLAQUE. PLAQUE SHALL �-
BE UV RESISTANT IF EXPOSED TO SUNLIGHT. „f `6IN .ore
STATE
3. DC CONDUCTORS SHALL BE RUN IN EMT AND SHALL BE LABELED, "CAUTION DC VERSION
CIRCUIT" OR EQUIV. EVERY 5 FT. DESCRIPTION DATE REV.
BLDG.PERMIT 09/03/2025 0
4. EXPOSED NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT
SHALL BE GROUNDED IN ACCORDANCE WITH 250.134 OR 250.136(A).
5. CONFIRM LINE SIDE VOLTAGE AT ELECTRIC UTILITY SERVICE PRIOR TO
CONNECTING INVERTER. VERIFY SERVICE VOLTAGE IS WITHIN INVERTER
VOLTAGE OPERATIONAL RANGE.
6. OUTDOOR EQUIPMENT SHALL BE NEMA-3R RATED OR BETTER.
PROJECT NAME
7. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT EXPANSION JOINTS AND w
ANCHOR CONDUIT RUNS AS REQUIRED PER NEC. w < o
0 o J
8. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL w J o o O
MEANS DESIGNED AND LISTED FOR SUCH USE, AND FOR ROOF MOUNTED � m oo Q
SYSTEMS, WIRING MUST BE PERMANENTLY AND COMPLETELY HELP OFF OF THE w � O
ROOF SURFACE. NEC 110.2 - 110.4 / 300.4 p 0 z o o }J LL
ti
Q mw 00 - 0
9. ALL ROOF PENETRATIONS MUST BE FLASHED. SIMPLY CAULKING DOES NOT (D C) -' z
SUFFICE. 0 0 0 0 � H
> > a =
Q U Q Q
SHEET NAME
ADDITIONAL NOTES
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-5
ENGINEERING DRAWING(mm) CS6.1-54TM-455H/I-V CURVES
A
Rear View Frame Cross Section
1514 _ --ts -- --- HARVESTPOW'
_ '.:�r CanadianSolar A-A /s -- HARVEST POWER LLC
1: --1 IIXX - 2941 SUNRISE HIGHWAY ISLIP
6 m5
n ------- -._ ----1 - TERRACE,NY 11752
=G 9, A A -35 19 _-1 - R �TEC TEL:(801)989-3585
Tlilt
hsite:wwwharvest ower.net
Hok -_ 7
rr1
8 S J 4 ---
Mounting Hole
0 �.
5 10 15 20 2s 3o 35 40 '5 50 5 10 15 20 25 35 45 50
P ■ l000 W/m� ■ •O" V
■ 600 W/ 25'C
■ 00 W/m'm' Y TATE 0�
■ 400W/m� 65 VERSION
__3s _ n3a 80 _ '- _3_J DESCRIPTION DATE REV.
TO P H i K u 6 (All-Black) Oea 2oow/m BLDG.PERMIT 09/03/2025 0
N-type TOPCon Technology
445 W '-' 470 W ELECTRICAL DATA STC* MECHANICAL DATA
CS6.1-54TM 445H 450H 455H12-2
460H 465H 470H Specification Data
C56.1-54TM-445 450 455 460 465(470H Nominal Max.Power(Pmax) 445 W 450 455 W460 W 465 W 470 W Ceil Type TOPCon cells
Opt Operating Voltage(Vmp)32.8 V 33.0 33.2 V33A V 33.6 V 33.8 V Cell Arrangement 108[2 X(9 X 6))
Opt Operating Current(Imp)13.59 A 13.66 13.7213.78 A 13.85 A 13.91 A 1800 x 1134 x 35 mm
Dimensions
Open Circuit Voltage(Voc) 38.7 V 38.9 39.1 V39.3 V 39.5 V 39.7 V (70.9 x 44.6 x 1.38 in)
_ . Weight 23 kg(50.71bs)
Short Circuit Current(Isc) 14.48 A 14.55 146114.69 A 14.77 A 14.86 A
MORE POWER / 25 I Industry Leading Product Warranty on Materials Module Front Cover 3.2 mm tempered glass with anti-ref-
ars and Workmanship* Module Efficiency 21.8% 22.096 22.3% 5% 22.8% 23.0% lective coating
Operating Temperature -40°C-+85°C Frame Anodized aluminium alloy
Module power up to 470 W J-Box IP68,3 bypass diodes
Module efficiency up to 23.0%
470 W Max.System Voltage 1500V QEC/UL)or 1000V(IEC/UL)
UL 617301500 Cable 4 mrr>2(IEC),12 AWG(UL)
TYPE 1
30 Linear Power Performance Warranty* ( v)orTYPE2(UL61730 PROJECT NAME
Module Fire Performance
Years 1 OOOV)or CLASS C(IEC 61730) Connector T6,MC4,MC4-EV02 or MC4-EV02A LU
r Excellent anti-LeTID&anti-PID performance. Max.Series Fuse Rating _ 25 A -Cable Length 1550 mm(61.0 in)(+
)/ U
Low power degradation,high energy yield 161 year power degradation no more than 1% Application Classification Class A (Including Connector) 1100 mm(43.3 in)(-) z Q
Subsequent annual power degradation no more than 0.4% Power Tolerance 0-+10 W � LLJ D O
_ _ Per Pallet 31 pieces � J
-Subject to the terms and conditions contained in the applicable Canadian Solar Limited ;--under Standard Test Conditions(STC)of irradiance of 1000 W/m2,spectrum AM 1.5 and cell tempe- - - -- --- -------- - ❑ O O
Lower temperature coefficient(Pmax):-0.29%/°C, Warranty Statement.Also this 2Syear limited product warranty is available only for pro-
�= increases energy yield in hot climate ducts installed and operating on rooftops in certain regions. ratureof25C. U Z CO O
. Per Container( 'H )744 pieces _
............................................................................................................................... W J O CD Q
MANAGEMENT SYSTEM CERTIFICATES* LLJ O a- O
C$ Lower LCOE&system cost I5090012 ELECTRICAL DATA 015/Quality management system I NMOT* TEMPERATURE CHARACTERISTICS 0 0 }- O J U)
ISO 14001:2015/Standards for environmental management system ❑ p
C56.1-54TM 445H 450H 455H 460H 465H 470H O
Z LL
ISO45001:2018/International standards for occupational health&safety Specification fication Data O }-IEC62941:2019/Photovoltaic module manufacturing quality system Nominal Max.Power(Pmax) 335 W 339 W 343 W 347 W 351 W 354 W z � -,1- O
-_- Temperature Coefficient(Pmax) -0.29%/°C Q m LLJ OO -
MORE RELIABLE Opt.Operating Voltage(Vmp)30.9 V 31.1 V 31.3 V 31.5 V 31.7 V 31.9 V C D O J Z
PRODUCT CERTIFICATES* -V 0 ----3 V -.9 V Temperature Coefficient(Voc) -0.25%/°C G Ln O
Opt Operating Current(Imp) 10.85 A 10.91 A 10.96 A 11.02 A 11.07 A 11.12 A O
IEC61215/IEC61730 TemperatureCoefflcient(Isc) 0.05%/°C 0 0 CD 0
IEC 61701/IEC 62716/IEC 60068-2-68 Open Circuit Voltage(Voc) 36.5 V 36.7 V 36.9 V 37.1 V 37.3 V 37.5 V Nominal Module Operating Temperature 42 t 3°C U _ (-
Minimizes micro-crack impacts Take-e-way p g p _-_
/e Short Circuit Current(Isc) 11.68 A 11.74 A 11.79 A 11.85 A 11.92 A 11.99 A ❑ (�
/ \ D •Under Nominal Module Operating Temperature(NMOT�irradiance of 800 W/mxspecuum AM 1.5, Z
Y� ambient temperature 20°C,wind speed 1 m/s. >
*�* H eavy snow load u p to 8100 Pa, *The specific certificates applicable to different module types and markets will vary,and PARTNER SECTION Q U Q
p you order or use.Please contact your local Canadian Solar sales representative to confirm . Q
wind load u t0 6000 Pa* therefore not all of the certifications listed herein will simultaneously apply to the products
.................................................................................................................
the specific certificates available for your Product and applicable in the regions in which
the products will be used. ' SHEET NAME
...............................................................................................................................
CSI Solar Co., Ltd.is committed to providing high quality solar SPEC SHEET
*The specifications and key features contained In this datasheet may deviate slightly from our actual
photovoltaic modules,solar energy and battery storage solu-
products due to the on-going innovation and product enhancement.CSI Solar Co.,Ltd.reserves the right
tions to customers.The company was recognized as the No.1 to make necessary adjustment to the Information described herein at any time without further notice. SHEET SIZE
module supplier for quality and performance/price ratio in the Please be kindly advised that PV modules should be handled and installed by qualified people who have
professional skills and please carefully read the safety and installation instructions before using our PV ANSI B
IHS Module Customer Insight Survey.Over the past 22 years,it modules.
4.................................................................................................................€
has successfully delivered over 100 GW of premium-quality solar 11�� X 17"
modules across the world.
_................................................................................................................................................................................................
*For detailed Information,please refer to the Installation Manual. Canadian Solar(USA)Inc. December 2023 1 All rights reserved I PV Module Product Datasheet v.1.1 C25-F23_P1_NA
..................................................................................................................................................................................................................................................-............
Canadian Solar(USA)Inc. SHEET NUMBER
1350 Treat Blvd.Suite 500,Walnut Creek,CA 94597 1 www.csisolar.com/na I service.ca@csisolar.eom PV-6
HARVESTPOW1
ENPHASE7 IQ7HS Microinverter HARVEST POWER LLC
2941 SUNRISE HIGHWAY ISLIP
' ••� - TERRACE,NY 11752
INPUT /P TEL (801)9119-3585
Commonly used module pairings' W 320-460 � (` w te:www.harvest ower.net
Module compatibility — 60-cell/120-half-cut-cell,66-cell/132-half-cut-cell, and 72-cell/144-half-cut-cell PV m •J �
Maximum input DC voltage V 59Ion
Peak power tracking voltage V 38-43 CPU)� Y
Operating range V 20-59 0
Minimum/Maximum start voltage V 30/59 �lb
Maximum input DC short-circuit current A 25
Maximum module Ig A 20 STATE
VERSION
ENPHASE
Overvoltage class DC port — II
• DESCRIPTION DATE REV.
DC port back-feed current A 0 BLDG.PERMIT 09/03/2025 0
PV array configuration _ 1.1 ungrounded array;no additional DC side protection required;AC side protection requires
Jim max.20 A per branch circuit
i OUTPUT DATA JAC)
Peak output power VA 384(1240 VAC, 69 @ 208 VAC
Maximum continuous output power VA 384 @ 240 VAC,1
69 @ 208 VAC
Nominal(L-L)voltage/Range2 V 240/211-264,208/183-229
Maximum continuous output current — 1.60 A(240 V) .77 A(208 V)
1 Q7 H S Microinverter Easy to install Nominal frequency Hz 60
Lightweight and simple Extended frequency range Hz 47-68
The high-powered,smart rid-read IQ7HS Microinverter with integrated MC4 Faster installation with improved,
9 Y 9 AC short-circuit fault current over three
connectors dramatically simplifies installation while achieving the highest system lighter two-wire cabling cycles Arms 4.82 PROJECT NAME
efficiency. Built-in rapid shutdown compliant Maximum units per 20 A(L-L)branch w
(NEC 2014,2017.2020.and 2023) circuit3 — 10(240 VAC).9(208 VAC) U
Productive and reliable Overvoltage class AC port — III z Q
Enphase AC port back-feed current mA 18 0 CD �
Optimized for high powered O
60-cell/120-half-cut-cell,66-cell/ Power factor setting — 1.0 U - LO O
O =
132-half-cut-cell.and 72-cell/ Power factor(adjustable) — 0.85 leading...0.85lagging LLf z OD O ~
144-half-cut-cell PV modules � Q
Part of the Enphase Energy System,the IQ7HS Microinverters extend the reliability More than a million hours of testing LLJ , O, n- O
I07HS Microinverters integrate with the standards set forth by previous generations Class II double-insulated enclosure CEC weighted efficiency % 97.0 @ 240 V.96.5 @ 208 V 0 0 >_ CD _J U)
IQ Gateway.IQ Battery,and the and undergo over a million hours of power- UL Listed MECHANICAL D, � C) zTA O > �
Enphase Installer App monitoring and on testing,enabling Enphase to provide an z cr F— O
LLJanalysis software. industry-leading warranty of up to 25 years. Ambient temperature range °C(°F) -40 to 60(-40 to 140) Q m � Op J Z
Smart grid-ready CC �
Relative humidity range % 4 to 100(condensing) G � F—
Complies with advanced grid support. 0 O O O O
DC connector type — Staubli MC4
voltage,and frequency ride-through (� _ 7—
—
requirements Dimensions(H•W x D) mm(in) 212(8.3)=175(6.9)-30.2 0.2)without bracket (�
Remotely updates to respond to z
CERTIFIED changing grid requirements Weight kg(Ib) 1.1(2.4) \ _
Configurable for varying rid profiles Cooling — Natural convection—no fans Q U Q Q
Connect PV modules quickly and easily I07HS Microinverters are UL Listed Meets CA Rule 21(UL 1741-SA)and Approved for wet locations — Yes 0
to the I07HS Microinverters that have as PV rapid shutdown equipment and IEEE 1547:2018(UL 1741-3B,3rd Ed.)for
integrated MC4 connectors. conform with various regulations when single-phase systems Pollution degree — PD3 SHEET NAME
installed according to the manufacturer's
instructions. SPEC SHEET
SHEET SIZE
'Pairing PV modules with wattage above the limit may result in additional clipping losses.See the compatibility calculator at enphase.com/installers/microinverters/calculator. ANSI B
m 2024 Enphase Energy.All rights reserved.Enphase,the e and CC logos,IQ and certain other marks listed at 2 Nominal voltage range can be extended beyond nominal if required by the utility. 11�� X 1 7��
enRhase.ccm/trademark-usage-guidelines are trademarks of Enphase Energy,Inc.in the U.S.and other countries. a Limits may vary.Refer to local requirements to define the number of microinverters per branch in your area.
Data subject to change. DSH-00562-1.0-EN-US-2024-08-02 DSH-00562-1.0-EN-US-2024-08-02
SHEET NUMBER
PV-7
�i
► ' 1 ' ' •PUNIRASOLARM0UNT . •�
I
.``g
BETTER DESIGNS
TRUST THE INDUSTRY'S BEST DESIGN TOOL CONCEALED UNIVERSAL �o j .. •
• 1 1 , , 1 1 1 . 1 . 1 •, , . 1 Start the design process for every project in our U Builder on-line design tool. ENDCLAMPS ® '
It's a great way to save time and money.
BETTER SYSTEMS --
Lei
ONE SYSTEM-MANY APPLICATIONS
Ouickly set modules flush to the,roof on sleep pitched roofs.Orient a large variety
of modules in Portrait or Landscape.Tilt the system up on flat or low slow roofs.
END CAPS INCLUDED
Components available in mill.clear.and dark finishes to optimize your design financials WITH EVERY ENDCLAMP --
`. and aesthetics.
BETTER RESULTS
MAXIMIZE PROFITABILITY ON EVERY JOB
CONCEALED Trust Unirac to help you minimize both system and labor costs from the time the job is
UNIVERSAL quoted to the time your teams get off the roof.Faster installs.Less Waste.More Profits.
CLAMPS UNIVERSAL SELF
:FUNIRAC BETTER SUPPORT STANDING MIDCLAMPS
25 WORK WITH THE INDUSTRIES MOST EXPERIENCED TEAM
Professional support for professional installers and designers.You have access to
our technical support and training groups.Whatever your support needs.we've got
OPTIONAL YEAR you covered.Visit Unirac.com/solarmount for more information. r
f RONT TRIM FULE-SYSTEPil I '
4 y
' WARRANTY
�� �' U-BUILDER ONLINE DESIGN �
t• 1 �� TOOL SAVES TIME& MONEY •
o BONDING&GROUNDING `, Visit design.unirac.com •
E � UL2703
MECHANICAL LOADING
YSTEMFIRE CLASSIFICATION •
UNIRAC CUSTOMER SERVICE MEANS THE HIGHEST LEVEL Of PRODUCT SUPPORT ;� ;, •
UNMATCHED CERTIFIED ENGINEERING BANKABLE DESIGN PERMIT
EXPERIENCE QUALITY EXCELLENCE WARRANTY TOOLS DOCUMENTATION
TECHNICAL SUPPORT CERTIFIED QUALITY PROVIDER BANKABLE WARRANTY
Unirac s technical support team is dedicated to answering Unirac is the only PV mounting vendur with ISO Doi t leave your project to chance,Unirac has the
questions&addressing issues in real time.An online certifications for 9001:2008.14001:2004 and OHSAS financial strength to back our products and reduceyour risk.
of
THE PROFESSIONALS' CHOICE FOR RESIDENTIAL RACKING seamy dfdecuments dtechnicaldng tasheetgreporis. 1800120m.which ndfuncean.Tesecertier cation st demonstrate
Have peace oh mind
ty.SOL RMOUNg you re covered by a25yding year
siampedletters andtechnicaldatasheetsgreatly for fit,form.andfunction.Thesecertihcationsdemonstrate exceptional quality.SOLARMOUNTiscoveredbya25year �
simplifies your permitting and project planning process. our excellence arid commitment to first class business practices. limited product warranty and a 5 year limited finish warranty.
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIilllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllll IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
BEST INSTALLATION EXPERIENCE•CURB APPEAL*COMPLETE SOLUTION•UNIRACSUPPORT ENHANCE YOUR REPUTATION WITH QUALITY RACKING SOLUTIONS BACKED BY ENGINEERING EXCELLENCE AND A SUPERIOR SUPPLY CHAIN
FOR QUESTIONS OR CUSTOMER SERVICE VISIT UNIRAC.00M OR CALL (505) 248 2702 PWQ(r18AUG,r1Pe!mr0U1`OAII FOR QUESTIONS OR CUSTOMER SERVICE VISIT UNIRAC.COM OR CALL (505) 248-2702
•
e Letter-NY
Tectonic Tectonic Unirac nicW #:1255724 HARVEST
Tectonic WO#:12557.24
August 12,2024 HARVEST POWER LLC
2941 SUNRISE HIGHWAY ISLIP
TERRACE,NY 11752
TEL:(801)989-3585
August 12, 2024 ■ Metal Roof: Standing Seam Attachments, PM-9000s, and PM Adjust Slotted website:www.harvest owernet
Unirac
• Tile Roof: Solar hooks, Flashkit Tile Replacement (TR) CHI ECT
Attn: Engineering Services Department The U-Builder Tool should be used under the responsible charge of a registeredt��`' �N
1411 Broadway Boulevard NE professional engineer required by the authority having jurisdiction. The design tool
Albuquerque, NM 87102-1545 and Unirac do not evaluate the existing roof structure, or the PV panels themselves. co
TEL: (505)242-6411 See the construction and installation drawings and manuals for additional information provided by Unirac. 0
�� �
RE: ENGINEERING CERTIFICATION LETTER FOR THE UNIRAC SOLARMOUNT (SM)
ROOF PV PANEL SUPPORT SYSTEM Sincerely,
pF NEW VERSION
STATE: NEW YORK Tectonic P�� A. c& y0 ST,q TION DATE REV.
TECTONIC WORK ORDER#: 12557.25 �; BLDG.PERMIT ostostzozs o
The Unirac SOLARMOUNT SM Photovoltaic Panel Su A( ) Support System is a proprietary
framed photovoltaic panel support system that is installed on a roof. Tectonic m w
z
Engineering Consultants, Geologists & Land Surveyors, D.P.C. (Tectonic) has
reviewed the SM design methodology along with the U-Builder tool; a Unirac online °0 07124g
design tool. The review included the following SM products, SM Light, Heavy Duty, SlO\A 08/12/2024
and Standard rail with both the standard and pro hardware.
Antonio A. Gualtieri, P.E.
Tectonic has determined that the design is a rational approach and follows the Executive Vice President
structural requirements of the following reference documents:
Codes/Standards:
• 2020 Building Code of New York State. PROJECT NAME
2018 International Building Code by International Code Council. LU
• ASCE/SEI 7-16 Minimum Design Loads for Buildings and Other Structures, by U Q
American Society of Civil Engineers with provisions from SEAOC PV-2-2017. LU0 o 0
■ 2020 Aluminum Design Manual, by Aluminum Association. p o
This letter certifies that the structural analysis of the racking members, connections, LU Z M o O=
H
and components directly related to Unirac's system are in compliance with the _j � o Q
above codes. The design methodology is acceptable under components and W = _ c- O
cladding loads associated with the building's roof structure when the system is O 0 } o J U)
installed in accordance with manufacturer specifications. If the loading criteria does 0 — Z CDj= IL
not meet Unirac's specifications, owner shall contact Unirac for a site-specific Q m LU 0000 O
certification. O o o
Attachments approved for the SM system to the structure include the following U r— O o O
and is installed per Unirac's U-Builder report and installation guides: C) 0 Z
■ Shingle Roof: L-Foot Flashkit Pro, Standoffs, Flashloc Comp, Flash Loc Duo, Q U Q Q
and Flash Kit Pro SB p
SHEET NAME
Project Contact Info Project Contact Info
1279 Route 300 1 Newburgh,NY 12550 1279 Route 300 1 Newburgh,W 12550 SPEC SHEET
845.567.6656 Tel 1 845.567.8703 Fax 845.567.6656 Tel 1 845.567.8703 Fax
SHEET SIZE
tectonicengineering.com tectorrcenginewing.com page 2 of 2 ANSI B
Equal opportunity Employer Equal Opportunity Employer
11" X 17"
SHEET NUMBER
PV-9